Permit NumberFIR04-00300
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 123 S AUTO DR
Project NameSPR CALVARY CHAPEL CLASSROOMS
Customer Number 
ePlanReview 
Description
CALVARY CHAPEL CHURCH CLASSROOMS * To extend an existing dry pipe system from the existing main building through a 6,459-ft/2 addition to an existing 4, 574-ft/2 one story Type V-B building, to create new church classrooms and a new bookstore. This facility will be fully fire sprinklered and have a fire alarms system installed. Fire sprinklers are used for area increase. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD03-02403.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/23/20049/23/20049/23/2004PPASS
DetailsTroy Cobbley
fire sprinkler finaled
INSP-Sprinkler Rough-in/Hydro8/26/20048/27/20048/27/2004PPASS
DetailsTroy Cobbley
24 hour air test passed 8/27/2004 2:04:10 PM
INSP-Sprinkler Rough-in/Hydro8/25/20048/26/20048/26/2004APASS
DetailsTroy Cobbley
200 lbs hydro test has passed. Started the 24 hour air test at 3:00 with 48psi on the gauge 8/26/2004 3:21:26 PM
INSP-Sprinkler Rough-in8/24/20048/25/20048/25/2004APASS
DetailsTroy Cobbley
Sprinkler piping is ok to cover. Contractor does not have the dry pendants yet. Temporary pendants installed for now. Eric and I spoke about modifications to the connection between the new system and the old. I verified with Bill this minor modification would not require submittals. 8/25/2004 11:23:46 AM
INSP-Sprinkler Rough-in7/15/20047/15/20047/15/2004PPASS
DetailsTroy Cobbley
Sprinkler piping above the hard lid areas are ok for cover. I also looked at the main and branchline sizing, hangers and earthquake bracing. They are ok as well. Sprig ups, drops and return bends have not been inspected since not all work is complete. 7/15/2004 2:33:21 PM