Permit Number | FIR04-00322 |
Status | Finaled |
Name |
TREASURE VALLEY FIRE PROTECTION
|
Site Address |
1161 W RIVER ST Unit: 310
|
Project Name | SPR-FOREST RIVER IX-3RD FLR |
Customer Number | |
ePlanReview | |
Description |
To replace existing standard sprinklers with QR type, and to relocate and add sprinklers to accommodate new walls, within the TI space. New hydraulic calculations are included for the most remote area of the building sprinkler system(on 3rd floor), to verify a density of 0.10 gpm over 1500 sq ft, using sprinkler head spacing up to 180 sq ft, with 1" dia. armovers from existing sprinkler head outlets.
The scope of the associated building permit BLD04-00813 is: BANNER BANK - FOREST ROVER IX - SUITE 310. This building is fire sprinklered to substitute for 1-hr fire-resistive construction. To remodel a 4,048 square foot office tenant space located on the 3rd floor of a 48,900 square foot building. Work is to include interior nonbearing walls, interior doors, interior windows, suspended ceilings, and interior finishes all per the approved drawings and the plan review conditions on file. In addition, the restrooms located on the 3rd floor will be upgraded to be accessible to the disabled. The location of fire sprinkler heads within this tenant space shall comply with NFPA 13-2002 as regulated by the Fire Department. **CJW**
|