Permit NumberFIR04-00358
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 200 N 4TH ST
Project NameSPR TERRACE PLAZA
Customer Number 
ePlanReview 
Description
(IDAHO CENTRAL CREDIT UNION)(TERRACE PLAZA) * To upgrade/modify the basement fire sprinkler system to meet current construction protection and extend fire sprinkler protection throughout the 1st, 2nd and 3rd floors. Basement fire sprinklers will be completely changed to Q.R.'s and added protection in all concealed combustible areas. The existing riser assembly will be modified to include a new supply main piped though and up into the existing floor janitor's closets with separate floor zone controls and the installation of a double backflow preventer with forward flow appurtenance which will double for a new main drain. A anti-freeze loop system will be installed in the drive-thru canopy. This project has been submitted and reviewed for a change in construction type, as a Type IIIB rather than Type IIIA construction type, since the building is not compliant with 1-hour construction. This fire protection work shall comply with the IFC 2000 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD03-01830.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/14/20059/14/20059/14/2005PPASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection7/15/20057/15/20057/15/2005PPART
DetailsForrest France
Provide seismic clearance at UG supply where it passes through the foundation wall, provide sinage at riser room door indicating its location.
INSP-Final Inspection6/21/20056/22/20056/22/2005APART
DetailsForrest France
Final pending inspection of heads in one room at the basement level to which access was denied, also need to provide seismic clearance at the underground supply where it passes through the foundation wall.
INSP-Sprinkler Rough-in/Hydro6/8/20056/8/20056/8/2005PPART
DetailsForrest France
Overhead hydrostatic test of basement, first floor, and antifreeze systems passed two hour test.
INSP-Sprinkler Rough-in4/11/20054/11/20054/11/2005PPART
DetailsTroy Cobbley
See plans with todays date for areas ok to cover. Resubmittals are required for changes in piping, lobby and room above ceiling
INSP-Sprinkler Rough-in3/23/20053/23/20053/23/2005PPASS
DetailsTroy Cobbley
Spoke to Mike on phone. Area in question on first floor is ok to cover 3/23/2005 4:00:54 PM
INSP-Sprinkler Rough-in2/25/20052/25/20052/25/2005PPART
DetailsTroy Cobbley
See approved plans for locations in basement where the sprinkler piping is ok to cover. 2/25/2005 3:28:01 PM
INSP-Sprinkler Rough-in2/14/20052/14/20052/14/2005PPART
DetailsTroy Cobbley
See approved plans for first floor locations ok to cover 2/14/2005 4:07:28 PM
INSP-Sprinkler Rough-in2/1/20052/2/20052/2/2005PPART
DetailsRick Jackson
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 2nd and 3rd floors hydro and r/i's all complete 2/2/2005 1:51:23 PM
INSP-Sprinkler Rough-in/Hydro1/31/20051/31/20051/31/2005PPART
DetailsRick Jackson
Mike; Phone #: ###-#### Internet Inspection Request from: Jan Rice 2nd floor r/i and hydro okay 1/31/2005 3:11:11 PM
INSP-Sprinkler Rough-in/Hydro10/19/200410/19/200410/19/2004PPART
DetailsRick Jackson
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Hydro okay on third floor and main feed from riser to third floor; still need resubmittals and will need to verify piping after approved 10/19/2004 3:39:55 PM
INSP-Sprinkler Rough-in10/15/200410/15/200410/15/2004PFAIL
DetailsRick Jackson
mike; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Verified piping on third floor hallway only - need resubmittals due to changes and using flexheads 10/15/2004 1:54:01 PM
INSP-Conference8/26/20048/26/20048/26/2004PPART
DetailsRick Jackson
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Met with Mike about the riser for floors - plans show in electrical closet but will not meet clearances from electrical panels per NEC; stair risers may work but will have to maintain IBC clearances at landings; plan modifications will be needed to reflect changes 8/26/2004 1:03:51 PM