Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR04-00364
StatusFinaled
Name PROTEX
Site Address 3434 W PASADENA DR
Project Namealm *School* Owyhee Elementary
Customer Number 
ePlanReview 
Description
To replace an existing fire alarm system. The required manual fire alarm system includes HVAC shutdown, fire/smoke damper control, door release and notification throughout.

8/27/2004 - Additional scope:

Duct detector added for RTU 7, in the nurses station.

A new NAC panel has been added to accommodate the NACs from the FACP. The NACs from the FACP will now be the "supervised" trigger for each of three NAC panels.

The existing smoke detectors in the corridors are being changed out to a Silent Knight, SLK-24F with HSB-224 base.

The school district has requested to use an existing Maxsys security panel (UL listed for fire alarm) as the dialer for the required monitoring by a remote supervising station. This is an acceptable solution as long as the Maxsys panel will send alarm and trouble. (No supervisory signals may be processed by the FACP as there is no means to transmit the signal to the remote supervising station.) Therefore, duct detectors must by an alarm signal. The Maxsys panel has an existing 12v 12 a-h battery back-up, which per the battery calcs should be sufficient for 24 hour supervisory and 5 minute alarm.

The associated building permit (BLD 04-00791) is to replace accordion and panel partitions with new non-load bearing partitions, upgrade fire alarm system and add a fire rated entry to serve the exit from the multipurpose room per approved plans and attachments. (Owyhee Elementary School)(Classroom remodels) *
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/28/20049/28/20049/28/2004PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 9/28/2004 at 10:21:00 AM. Contact: ###-####.
INSP-Final Inspection9/20/20049/22/20049/22/2004PFAIL
DetailsRick Jackson
This is Grants Cell we need to do thei after 3:30 BECAUSE OF SCHOOL BEING IN SESSION THANK YOU HAVE A GREAT DAY!; Phone #: ###-#### Internet Inspection Request from: Terry Owsley All items corrected except the smoke detectors not replaced with Silent Knight 9/22/2004 4:47:31 PM
INSP-Final Inspection8/20/20048/20/20048/20/2004APART
DetailsTroy Cobbley
A temporary occupancy was given with Dave Millers permission until the fire alarm plans have been resubmitted and the project inspected. 8/20/2004 1:44:47 PM
INSP-Final Inspection8/16/20048/17/20048/17/2004PFAIL
DetailsTroy Cobbley
Provide Knox key box. Provide duct smoke detector on HVAC unit #2 for the office area. Sync strobes in the multipurpose room. Test second smoke detector on zone #5 HVAC unit. Verify battery calculations on the facp and nac panels. Verify wiring integrity between nacs and facp. Verify dedicated circuits. Verify that alarm only output is permissable with plan reviewer. 8/17/2004 4:08:20 PM
INSP-Final Inspection8/11/20048/13/20048/13/2004PNR
DetailsRick Jackson
This is Grants Cell; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Receved call from Grant and they are not ready for inspection; will reschedule when ready 8/13/2004 12:26:50 PM