INSP-Final Inspection | 9/28/2004 | 9/28/2004 | 9/28/2004 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/28/2004 at 10:21:00 AM. Contact: ###-####.
|
INSP-Final Inspection | 9/20/2004 | 9/22/2004 | 9/22/2004 | P | FAIL |
Rick Jackson
|
|
|
This is Grants Cell we need to do thei after 3:30 BECAUSE OF SCHOOL BEING IN SESSION THANK YOU HAVE A GREAT DAY!; Phone #: ###-#### Internet Inspection Request from: Terry Owsley All items corrected except the smoke detectors not replaced with Silent Knight 9/22/2004 4:47:31 PM
|
INSP-Final Inspection | 8/20/2004 | 8/20/2004 | 8/20/2004 | A | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given with Dave Millers permission until the fire alarm plans have been resubmitted and the project inspected. 8/20/2004 1:44:47 PM
|
INSP-Final Inspection | 8/16/2004 | 8/17/2004 | 8/17/2004 | P | FAIL |
Troy Cobbley
|
|
|
Provide Knox key box. Provide duct smoke detector on HVAC unit #2 for the office area. Sync strobes in the multipurpose room. Test second smoke detector on zone #5 HVAC unit. Verify battery calculations on the facp and nac panels. Verify wiring integrity between nacs and facp. Verify dedicated circuits. Verify that alarm only output is permissable with plan reviewer. 8/17/2004 4:08:20 PM
|
INSP-Final Inspection | 8/11/2004 | 8/13/2004 | 8/13/2004 | P | NR |
Rick Jackson
|
|
|
This is Grants Cell; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Receved call from Grant and they are not ready for inspection; will reschedule when ready 8/13/2004 12:26:50 PM
|