Permit Information
Permit NumberFIR04-00377
StatusFinaled
Name CRANE ALARM COMPANY
Site Address 5680 W GAGE ST
Project Namealm - J&A Enterprises
Customer Number 
ePlanReview 
Description
To replace an existing fire alarm system. The required sprinkler monitoring fire alarm system includes HVAC shutdown, fire/smoke damper control, manual pull stations, non-required automatic detection and notification throughout.

8/13/2004 - Revised scope, Fire/smoke dampers have been deleted and two more HVAC units have been installed requiring HVAC shutdown, therefore the required sprinkler monitoring fire alarm system includes HVAC shutdown, manual pull stations, non-required automatic detection and notification throughout.

The associated building permit (BLD 04-00495) is to remodel an existing 6,420 square foot building that is used as a medical office and for outpatient medical procedures. The number of persons incapable of self-reservation at any one time is limited to five (5). The medical gas system is existing and will be altered. Work is to include 2 restrooms accessible to the disabled, interior nonbearing walls, altered suspended ceilings, millwork, and interior finishes all per the approved drawings, engineering, and plan review report on file. An interior 1-hr wall is due to the owner's request and is NOT a requirement of the building code. The location of fire sprinkler heads shall comply with NFPA 13 as regulated by the Fire Department. **CJW** (J & A ENTERPRISES) This building is fire sprinklered.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/24/20048/24/20048/24/2004APASS
DetailsTroy Cobbley
Fire alarm finaled
INSP-Final Inspection8/18/20048/20/20048/20/2004ACANC
DetailsTroy Cobbley
Stopped at project. Contractor not ready to go until next week. 8/20/2004 8:20:21 AM
INSP-Final Inspection8/10/20048/10/20048/10/2004PPASS
DetailsTroy Cobbley
fire alarm finaled 8/10/2004 4:02:11 PM
INSP-Final Inspection8/6/20048/9/20048/9/2004ACANC
DetailsTroy Cobbley
PAT; Phone #: ###-#### Internet Inspection Request from: Annette Moore
INSP-Alarm Testing8/4/20048/6/20048/6/2004AFAIL
DetailsTroy Cobbley
Provide approved door hardware on doors marked on drawing sheet A1.1. Provide exit discharge illumination per building review notes #22. Install ceiling tile at sprinkler pendants. Test duct detectors. Relocate ducting at duct detector #1. Provide 30cd strobes in rooms as marked on plans and measure EOL voltage. Provide map at FACP 8/6/2004 1:57:55 PM
INSP-Final Inspection8/5/20048/6/20048/6/2004PCANC
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 8/5/2004 at 10:34:50 AM. Contact: ###-####.
INSP-Final Inspection7/30/20048/3/20047/30/2004ACANC
DetailsTroy Cobbley
pat; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Inspection cancelled from web by: Aimee Hughes