Permit Information
Permit NumberFIR04-00387
StatusFinaled
Name SYNERGY ENGINEERS
Site Address 420 W MAIN ST Unit: 402
Project Namealm - VELTEX BLDG-4TH/5TH FLRS
Customer Number 
ePlanReview 
Description
To provide multiple station smoke detectors in a residence per IFC and NFPA 72 and to extend the audible component of the existing building fire alarm system into the residence (4th and 5th floors). The required manual fire alarm system includes sprinkler monitoring, required automatic detection, HVAC shutdown, fire/smoke damper control, elevator recall/shutdown and notification throughout.

The associated building permit (BLD 03-02056) is to construct a new 4,338 sq.ft. two story condominium residential unit on the 4th and 5th floors. The fourth floor is approximately 2,388 sq.ft and the fifth floor is approximately 1,950 sq.ft. Work to include the installation of the HVAC, plumbing, electrical interior walls and cabinets. NOTE: The installation of a NFPA 13 fire sprinkler system is required for story increase and can not be used for any other purposes. All construction per the approved plans and attached comment list. MJP MICHAEL RESIDENCE)(VELTEX BLDG-UNIT 402)

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/10/20055/10/20055/10/2005APASS
DetailsForrest France
Fire alarm finaled.
INSP-Final Inspection5/4/20055/5/20055/5/2005APART
DetailsForrest France
Final pending test verification of sprinkler waterflow alarm and updated alarm map at panel.
INSP-Final Inspection5/3/20055/4/20055/4/2005AFAIL
DetailsForrest France
Tested audible fire alarms- need signal verification. Voltage drop OK. No smoke detector at stairwell top. Wrong type detector at kitchen hallway. Need to test all smoke detectors. Need to test waterflow alarms.
FIR-Aging Inspection10/12/200410/12/200410/12/2004 PASS
DetailsRick Jackson
In progress 10/12/2004 7:06:01 AM