Permit Information
Permit NumberFIR04-00393
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 10095 W EMERALD ST
Project NameSPR EMERALD TECH. BLD. #10
Customer Number 
ePlanReview 
Description
Emerald Tech Center Building #10 (Shell Only)- To install the underground fire service supply and overhead fire sprinkler suppression system in a new 11,504-ft/2, one story, concrete tilt-up office and warehouse shell building. The 6" C-900 PVC underground service is connected near the property line to a 10" looped supply following N. Ancestor and runs approximately 144-ft. west and then north into the building. Class 50 Ductile Iron will penetrate through the floor in Mechanical room #102 to the systems single riser assembly. The overhead system is incorporating E.C. heads for OH-2 occupancy, limiting this structure to where the quantity and combustibility of contents may be considered moderate to high with miscellaneous commodities classified as Class I through III, palletized, in bin boxes, shelf or open shelf racks which cannot exceed 12'-0". Commodities of Class IV in palletized, in bin boxes or shelf (no racks) cannot exceed 10'-0", unless system is redesigned with 500 gpm outside hose demand. Group "A" Plastics in open shelf racks, solid pile, palletized, bin boxes or shelf storage cannot exceed 5'-0" with exceptions. Miscellaneous tire storage on floor, on tread or on side, in single or double or multirow racks on tread or flat cannot exceed 5'-0" with exception. Each as reference in NFPA 13:12.1.10.1.1. Any racking or open use of commodities exceeding these heights cannot be permitted with separate review. This is a shell permit only and no occupancy is allowed under this permit. A separate tenant improvement permit will be required to finish this building for occupancy. This building is fully fire sprinklered. The sprinklers are used for area increase. All fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD04-00871.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in/Hydro11/10/200411/12/200411/12/2004APASS
DetailsTroy Cobbley
Fire sprinkler finaled 11/12/2004 12:49:55 PM
INSP-Conference11/3/200411/4/200411/4/2004PCANC
DetailsTroy Cobbley
INSP-Sprinkler Rough-in/Hydro9/16/20049/17/20049/17/2004APASS
DetailsTroy Cobbley
Underground supply piping is ok to cover. Taps have not been made yet. 9/17/2004 4:30:04 PM
INSP-Sprinkler Rough-in7/22/20047/23/20047/23/2004APART
DetailsTroy Cobbley
Inspection was for stub-out only. Plans show 8" but 6" was installed. Per conversation with Bill Alexander 6" will be OK as long as this is supported with revised hydraulic calculations. Stub-out is OK to bury. 7/23/2004 12:24:51 PM