Permit Information
Permit NumberFIR04-00420
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 350 N MILWAUKEE ST Unit: 1159
Project NameSPR BROOKSTONE BTS - #1159
Customer Number 
ePlanReview 
Description
(BROOKSTONE)(BOISE TOWNE SQUARE-SPACE 1159) To modify and add fire sprinkler is the remodel of a 2,773-ft/2 retail space on the lower level for new mercantile tenant, and a 500-ft/2 portion of tenant space #1155 for a remote storage area. The work includes changing and relocating out 36 existing dropped head with installing new standard concealed Q.R. sprinklers, 2 standard coverage, Q.R., semi-recessed head added in the restroom and the (separated) corridor entry, 3 standard coverage Q.R. uprights added in the New Sales area, and 6 standard coverage and Q.R. uprights added to the new remote storage room. All work is related to the construction of partitions, installation of new suspended ceiling, lighting, a new tenant restroom. This building is fully fire sprinklered and contains a smoke evacuation system. The smoke evacuation system shall remain operational as originally installed under the 1985 UBC. This fire protection work shall comply with the IFC 2000 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-01082.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/19/20048/19/20048/19/2004APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection7/27/20047/28/20047/28/2004AFAIL
DetailsTroy Cobbley
need ceiling tile and canopies for final 7/28/2004 12:13:13 PM
INSP-Sprinkler Rough-in7/27/20047/28/20047/28/2004APASS
DetailsTroy Cobbley
sprinkler piping is ok to cover 7/28/2004 12:12:52 PM
INSP-Sprinkler Rough-in7/22/20047/23/20047/23/2004PPART
DetailsTroy Cobbley
Hard lid areas ok to cover 7/23/2004 3:44:22 PM