INSP-Final Inspection | 7/27/2005 | 7/27/2005 | 7/27/2005 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 9/28/2004 | 9/29/2004 | 9/29/2004 | A | FAIL |
Troy Cobbley
|
|
|
Upright sprinkler heads which are spaced too far off of the exterior wall in the cavity have not been addressed. Small room rule can not be used. See nfpa 13; 3.3.20 for definition of a small room. Must have walls and a ceiling. Reinspection fee for fourth inspection for same item applied. 9/29/2004 10:06:46 AM
|
INSP-Final Inspection | 9/23/2004 | 9/24/2004 | 9/24/2004 | A | FAIL |
Troy Cobbley
|
|
|
Approved plans not on site. Per Adam they are in the principals office. The principal, Robert Wehde and I looked in his office and could not find the plans. Inspection failed. Re-inspection fee applied to this project. 9/24/2004 9:30:52 AM
|
INSP-Final Inspection | 9/23/2004 | 9/24/2004 | 9/24/2004 | A | FAIL |
Troy Cobbley
|
|
|
Approved plans not on site. Per Adam they are in the principals office. The principal, Robert Wehde and I looked in his office and could not find the plans. Inspection failed. Re-inspection fee applied to this project. 9/24/2004 9:30:52 AM
|
INSP-Final Inspection | 9/9/2004 | 9/9/2004 | 9/9/2004 | P | FAIL |
Troy Cobbley
|
|
|
Resubmit plans per review note #8. The addition of the rooftop unit has blocked coverage of the upright sprinkler head. Per the sprinkler head data sheet it appears that three types of sprinkler heads are being used. A 3/8" a 1/2" and a 3/4" are not crossed out on the data sheet. Specify which head is being used and in which location. Provide info and SIN number on the resubmittals. Provide access to the sprinkler heads such as a ladder for verification of specific head type and correct esch. Upright sprinkler heads have less than 1" clearance from ceiling to deflector. See NFPA 13; 8.6.4.1.1.1. Atleast one of the pipe hangers appear to be screwed into partical board above the ceiling. Provide verification this is acceptable and verification the other hangers meet NFPA 13 requirements. Upright heads are spaced 8'-6" off of the exterior wall in the concealed spaced. Provide verification "small room rule" can also be "small cavity rule" or add/relocate uprights. 9/9/2004 3:03:13 PM
|