Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR04-00519
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 199 N CAPITOL BLVD Unit: 707
Project Namealm - Tweliger TI SUITE 707
Customer Number 
ePlanReview 
Description
To provide required single station smoke detection and audible notification in a residence located in a high rise. The required manual fire alarm system includes HVAC shutdown, elevator recall/shutdown, fire/smoke damper control, door release and notification throughout.

The associated building permit (BLD 04-01426) is to remodel an existing 1,006 square foot residential condominium for a new tenant. This condominium is located on the 7th floor of an existing 112,000 square foot, 11 story high-rise building. Work is to include interior nonbearing walls, two restrooms, millwork, and interior finishes all per the approved drawings and the plan review report on file. The location of fire sprinkler heads shall comply with NFPA 13-2002 as regulated by the Fire Department. **CJW**- (R. J. TWILEGAR RESIDENCE - WASHINGTON MUTUAL BLDG - STE 707) This building is fire sprinklered because it is a high-rise.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/6/200412/6/200412/6/2004PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/6/2004 at 9:06:16 AM. Contact: ###-####.
INSP-Conference11/12/200411/12/200411/12/2004APART
DetailsRick Jackson
Per Sam Rogers the detectors in the space will be a combo smoke/heat detector as this the type of system throughout the exsisting R occupancies; the smoke is local to the room and the heat generates general alarm; this info was passed on the Brian and Chris of Simplex 11/12/2004 10:56:25 AM
INSP-Final Inspection11/9/200411/12/200411/12/2004AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 11/9/2004 at 12:48:42 PM. Contact: ###-####. Single station alarm in room generate building alarm - not per matrix; speakers operated properly 11/12/2004 10:23:49 AM