INSP-Final Inspection | 8/5/2005 | 8/8/2005 | 8/8/2005 | A | PASS |
Troy Cobbley
|
|
|
Fire sprinkler permit finaled
|
INSP-Final Inspection | 7/19/2005 | 7/20/2005 | 7/20/2005 | A | FAIL |
Troy Cobbley
|
|
|
Need to verify that the exposed combustibles located above the outside canopies has met requirements of NFPA 13 for combustible concealed spaces.
|
INSP-Final Inspection | 6/29/2005 | 7/1/2005 | 7/1/2005 | A | PART |
Troy Cobbley
|
|
|
Trip tested Dry System #1 and #2. Both sent in the correct alarm signals. Contractor still needs to correct overspaced and blocked heads under canopy, wrong air compressors installed, butterfly control valve on dry system #1 broke, need to blank off the switches controlling the air compressors, need to trip test the east dry system.
|
INSP-Sprinkler Rough-in/Hydro | 6/29/2005 | 6/30/2005 | 6/30/2005 | P | PASS |
Troy Cobbley
|
|
|
Hydro test for dry system #1 and #2 overhead systems and the two east branchlines under the canopy passed.
|
INSP-Sprinkler Rough-in | 6/23/2005 | 6/24/2005 | 6/24/2005 | P | PART |
Forrest France
|
|
|
Overhead main piping is good for cover except at trapeze nw side sheet fp2 where retaining strap is not attatched and at three locations where 4" main passes through block wall without proper seismic clearance. Also, exposed branch lines on roof must meet req. of NFPA 13 8.15.3.2.3.
|
INSP-Sprinkler Rough-in | 5/10/2005 | 5/12/2005 | 5/12/2005 | A | PART |
Troy Cobbley
|
|
|
The sprinkler piping for the exterior canopies is ok to cover. There is wood in areas above the ceiling in these exterior canopies. I notified the sprinkler contractor and the general contractor that this would have to be addressed since there are no upri
|
INSP-Conference | 5/9/2005 | 5/10/2005 | 5/10/2005 | A | DONE |
Troy Cobbley
|
|
|
Looked at high canopy. It will require sprinkler coverage for concealed combustible space per NFPA 13 unless exceptions can be met
|