Information based on query as of Saturday, June 29, 2024.
Permit Information
Permit NumberFIR04-00547
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 6325 N CLOVERDALE RD
Project NameSPR UG SPRINGHILL MARRIOTT
Customer Number 
ePlanReview 
Description
Springhill Suites Marriott Hotel - To install approximately 200 feet of 6" C-900 DR-14 PVC tapped near the northeast corner of the property, running west 193 feet and south approximately 10 feet under the footing to a fire sprinkler control room, then up through the finish grade floor with Ductile Iron Class 50 to a M.J. Adapter. This is a dedicated fire service supply service to a new 66,322-ft/2 four story, wood framed, 119 unit motel with 7,100-ft/2 meeting rooms, indoor spa, lobby area and food prep kitchen and a 1,720-ft/2 covered porte-cochere for area increase. This fire sprinkler underground supply work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD04-01267.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/13/20055/13/20055/13/2005PPASS
DetailsTroy Cobbley
Fire sprinkler finaled
INSP-Supply line flush5/3/20055/4/20055/4/2005APASS
DetailsTroy Cobbley
Underground flush and forward flush passed
INSP-Sprinkler Rough-in/Hydro10/20/200410/21/200410/21/2004APASS
DetailsTroy Cobbley
Undergrond hydro test passed 10/21/2004 12:16:39 PM
INSP-Sprinkler Rough-in/Hydro10/20/200410/20/200410/20/2004APASS
DetailsTroy Cobbley
Remaining underground supply piping is ok to cover. Dave Miller has given Shilo the ok to have the underground partialy covered by the building slab and the stub-in relocated from the electrical room to the hot water heater room. 10/20/2004 7:57:39 AM
INSP-Sprinkler Rough-in/Hydro10/12/200410/13/200410/13/2004ACANC
DetailsTroy Cobbley
Forrest is the formeman on site. This is for an underground inspection.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
INSP-Sprinkler Rough-in/Hydro10/13/200410/13/200410/13/2004PPART
DetailsTroy Cobbley
Underground supply line is ok to cover to 20 feet past the 90 bend. Resubmittal is required since piping was not installed as shown on the approved plans. Piping is run under slab to a new location. 10/13/2004 2:16:59 PM