Permit Information
Permit NumberFIR04-00552
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 4444 W GINZEL ST
Project NameSPR WALLACE RESIDENCE
Customer Number 
ePlanReview 
Description
WALLACE RESIDENCE-SLEIGHT CONSTRUCTION, INC. * To construct install an NFPA 13D (modified) fire sprinkler system in a new 3,174-ft/2, three story single family dwelling. Modified relates to fire sprinkler protection along common walls and ceilings of occupied residential living space. Any and all NFPA 13D systems shall be equipped with an alarm initiating device, commonly referred to as a flow switch and an outside annunciating device. The lower level is: 812-ft/2; the main level is: 2,022ft/2 an upper level is: 340ft/2. All fire sprinkler work including a duel service underground supply and related, including the fire sprinkler system backflow prevention device (to be provided by others), shall be per NFPA 13D, plans, documents, engineered/red-lined plans and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD04-01262.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/13/20054/14/20054/14/2005APASS
DetailsTroy Cobbley
Fire sprinkler finaled
INSP-Final Inspection3/24/20053/28/20053/28/2005PFAIL
DetailsTroy Cobbley
Water meter is the wrong size, two pendants in the basement are too close to soffits. Still need to do all of the final signoff items. 3/28/2005 12:11:28 PM
INSP-Final Inspection3/15/20053/17/20053/17/2005ACANC
DetailsTroy Cobbley
Per Chris a dry sidewall has been broken. Inspection to be rescheduled. 3/17/2005 10:38:35 AM
INSP-Supply line flush3/1/20053/4/20053/4/2005APASS
DetailsTroy Cobbley
Underground flush ok 3/4/2005 1:11:28 PM
INSP-Sprinkler Rough-in/Hydro12/20/200412/20/200412/20/2004APASS
DetailsTroy Cobbley
Sprinkler piping in the entry and main corridor is ok to cover
INSP-Sprinkler Rough-in12/13/200412/14/200412/14/2004APART
DetailsTroy Cobbley
Sprinkler rough-in is passed for the overhead system. Underground has not been verified. Tenting is ok except for the entry/central corridor area which was not complete yet. 12/14/2004 11:40:02 AM