Permit Information
Permit NumberFIR04-00592
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 5598 N QUAIL SUMMIT PL
Project NameSPR WILLIAM KEOUGH RES
Customer Number 
ePlanReview 
Description
WILLIAM KEOUGH RESIDENCE * To install an NFPA 13D (Modified) fire sprinkler system which includes fire sprinkler barrier protection between garage and dwelling in a 3,495-ft/2 one story single family dwelling with a 528-ft/2 attached two car garage. This NFPA 13D systems shall be equipped with an alarm initiating device, commonly referred to as a flow switch connected to an outside alarm device. All fire sprinkler work and related, which includes dual use, single service water supply and system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD04-01201.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/2/20053/2/20053/2/2005PPASS
DetailsTroy Cobbley
Fire sprinkler finaled 3/2/2005 4:50:05 PM
INSP-Final Inspection2/24/20052/25/20052/25/2005AFAIL
DetailsTroy Cobbley
John; Phone #: ###-#### Internet Inspection Request from: Jan Rice

U.G. Flush OK
Failed:
1. 3/4" meter installed, (requires 1" per calcs).
2. Inspectors test failed. Line malfunction (cracked 1/2" adapter).
INSP-Sprinkler Rough-in10/28/200410/29/200410/29/2004APART
DetailsTroy Cobbley
Inspection was for overhead sprinkler roughing and tenting. Overhead sprinklers are ok to cover. Underground supply piping is ok except for the water meter is not the right size. Its 3/4" not 1" as required. 10/29/2004 1:59:13 PM