Permit Information
Permit NumberFIR04-00634
StatusFinaled
Name ADT SECURITY SERVICES INC
Site Address 8050 W NORTHVIEW ST
Project Namealm - Sunhealth Hospital
Customer Number 
ePlanReview 
Description
To replace an existing fire alarm system. The required manual fire alarm system includes sprinkler monitoring, door release and notification throughout.

5/10/2005 - The kitchen building plans indicates two spaces that appeared to be closets. Upon inspection, the spaces were found to be restrooms. This plan modification adds visual notification to each restroom, revises the plans, riser, battery and voltage drop calculations.

There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/12/20108/18/20108/20/2010APASS
DetailsTroy Cobbley
Permit finaled
INSP-Conference7/27/20108/4/20108/11/2010ADONE
DetailsTroy Cobbley
Follow up conference with Keith (head of maintenance), on site, for project status and he stated that ADT would be contacting me.
INSP-Conference7/27/20107/27/20107/27/2010PDONE
DetailsTroy Cobbley
I spoke to the on site maintenance director named Keith about getting this permit finished. He was going to contact the fire alarm vendor. I set up a follow up inspection for next week.
INSP-Conference7/7/20107/7/20107/7/2010PDONE
DetailsTroy Cobbley
I went over the outstanding issues as per the permit history with Keith at ADT.
FIR-Aging Inspection3/17/20103/17/20103/24/2010 NR
DetailsTroy Cobbley
Permit information forwarded to Stephanie and to Scott for further action.
INSP-Final Inspection4/12/20054/13/20054/13/2005AFAIL
DetailsTroy Cobbley
Two a/v's are mounted too high. Provide additional a/v's in the restrooms, as marked on plans,and any other common areas. Test smoke detector at the panel. Provide verification of note #14.
INSP-Final Inspection4/7/20054/8/20054/8/2005PFAIL
DetailsTroy Cobbley
Resubmitted plans still do not match sizing or routing as installed. Fix it or resubmit it. Riser on plans shows steel. As installed its half steel and half plastic. Water meter is wrong size. Reinspection fees are being applied.
FIR-Aging Inspection3/29/20053/29/20053/29/2005 NR
DetailsTroy Cobbley
work in progress 3/29/2005 11:17:26 AM