Permit Information
Permit NumberFIR04-00684
StatusFinaled
Name IDAHO FIRE PROTECTION
Site Address 1426 S ENTERTAINMENT AVE
Project NameSPR OXFORD SUITES HOTEL
Customer Number 
ePlanReview 
Description
OXFORD SUITES HOTEL * To install the underground fire service supply, standpipe and overhead fire sprinkler protection systems in a new 91,785-ft/2, four story, with a basement, 132 room suite hotel. The basement is 17,287-ft/2 and contains, conference rooms, lounge, full service restaurant with kitchen. The first floor is 21,164-ft/2 contains the indoor swimming pool, spa, lobby area and 30 guest room. The second floor is 20,084-ft/2 contains 32 suites. The third floor is 21,164-ft/2 contains 39 suites and the forth floor is 17,287-ft/2 contains 31 suites. This building is fully fire sprinklered for area increase. The fire sprinkler systems and standpipe work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD04-00640.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/18/20061/18/20061/19/2006APASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in/Hydro1/10/20061/11/20061/11/2006PPASS
DetailsTroy Cobbley
Dry system trip test and forward flush passed.
INSP-Sprinkler Rough-in/Hydro1/10/20061/10/20061/10/2006APART
DetailsTroy Cobbley
Above ground hydro tests passed. Sprinkler devices on wet sytem passed alarm inspection.
INSP-Sprinkler Rough-in/Hydro1/6/20061/9/20061/9/2006PCANC
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 1/6/2006 at 2:06:03 PM. Contact: ###-####.
INSP-Sprinkler Rough-in12/30/20051/3/20061/3/2006AFAIL
DetailsTroy Cobbley
The sprinkler pendant just inside of the laundery room door is still overspaced. Piping (cpvc) in the mechanical room under the north stairs is exposed and needs to meet installation guide.
INSP-Sprinkler Rough-in12/22/200512/22/200512/23/2005AFAIL
DetailsTroy Cobbley
Sprinkler pendants in basement laundry room are overspaced. A separation is needed in the attic area between the washing machines and the open laundry area.
INSP-Sprinkler Rough-in12/21/200512/21/200512/22/2005PDEFR
DetailsForrest France
Inspection to be completed 12/ 22 per agreement with contractor.
INSP-Sprinkler Rough-in/Hydro11/28/200511/28/200511/28/2005APART
DetailsForrest France
Overhead rough-in at the basement confrence room is good for cover, one head at the NW corner is within 1' of a heat diffuser and a can light (may need an intermediate temp. head at this location).
INSP-Sprinkler Rough-in/Hydro11/22/200511/23/200511/23/2005ACANC
DetailsTroy Cobbley
No time for inspection
INSP-Sprinkler Rough-in/Hydro11/21/200511/22/200511/22/2005ACANC
DetailsTroy Cobbley
No time for inspection
INSP-Sprinkler Rough-in/Hydro9/12/20059/12/20059/12/2005APART
DetailsTroy Cobbley
Main lobby is ok to cover. Basement east side of main corridor is ok to cover.
INSP-Sprinkler Rough-in/Hydro8/24/20058/24/20058/24/2005PPART
DetailsForrest France
Overhead rough-in for the basement area from column lines 3 through 14 on the west side of the corridor as marked on sheet FP2 of the approved plans is acceptable to cover.
INSP-Sprinkler Rough-in/Hydro7/29/20057/29/20057/29/2005PPASS
DetailsTroy Cobbley
Swimming pool area piping ok to cover
INSP-Sprinkler Rough-in/Hydro7/15/20057/15/20057/15/2005PPASS
DetailsTroy Cobbley
Canopy is ok to cover. Eq bracing and upright have been added
INSP-Sprinkler Rough-in/Hydro7/11/20057/11/20057/11/2005PFAIL
DetailsTroy Cobbley
Inspection was for the drive through canopy. Need eq bracing for the sprig ups and one additional upright at the east overbuild. Also the third and second floor corridors are ok to cover.
INSP-Sprinkler Rough-in/Hydro6/16/20056/17/20056/17/2005PPART
DetailsForrest France
Overhead rough-in basement area CPVC mains and branch lines are OK to cover.
INSP-Supply line flush6/16/20056/17/20056/17/2005PPART
DetailsForrest France
Underground fire supply line flush satisfactory.
INSP-Sprinkler Rough-in6/14/20056/14/20056/14/2005PPART
DetailsTroy Cobbley
Ok to cover the conference room and corridor in the basement.
INSP-Sprinkler Rough-in/Hydro6/13/20056/13/20056/13/2005PFAIL
DetailsTroy Cobbley
Plans do not match installation
INSP-Supply line flush6/13/20056/13/20056/13/2005PFAIL
DetailsTroy Cobbley
No water to perform flush. Bill Thompson with United Water was contacted and the fire hydrants were put in service. Fire sprinkler contract needs to get service order so fire supply can become active.
INSP-Sprinkler Rough-in/Hydro5/24/20055/24/20055/24/2005PPASS
DetailsTroy Cobbley
First floor hydro test passed. Guest room sprinkler piping is ok to cover
INSP-Sprinkler Rough-in/Hydro5/2/20055/3/20055/3/2005APART
DetailsTroy Cobbley
Looked at the fourth floor corridor piping. Notified Tom that resubmitals will be required.
INSP-Sprinkler Rough-in4/21/20054/22/20054/22/2005APART
DetailsTroy Cobbley
Second floor sprinkler piping is ok to cover except corridor, pool area and central lobby area
INSP-Sprinkler Rough-in/Hydro4/20/20054/21/20054/21/2005PPASS
DetailsForrest France
Second floor, guest rooms only, hydro. test satisfactory.
INSP-Sprinkler Rough-in4/20/20054/20/20054/20/2005PPASS
DetailsTroy Cobbley
tom ###-#### Sprinkler piping at the north and south ends of the third floor is ok to cover.
INSP-Sprinkler Rough-in/Hydro4/18/20054/19/20054/19/2005AFAIL
DetailsTroy Cobbley
Inspection was for tenting on the third floor. Tenting failed. Need to re-inspect
INSP-Sprinkler Rough-in/Hydro3/26/20053/28/20053/28/2005APART
DetailsTroy Cobbley
Hydro test for the standpipe and the third floor failed. Rough-in for the fourth floor sidewalls in rooms passed. 3/28/2005 12:03:46 PM
INSP-Sprinkler Rough-in/Hydro3/16/20053/16/20053/16/2005APASS
DetailsTroy Cobbley
Attic system roughin is ok. This includes the eaves on the third floor. Changes have been made to the plans that will require resubmittals. This includes an extra layer of piping and heads in the tower, a main re route at the north end and the drive through 3/16/2005 1:22:51 PM
INSP-Supply line flush3/16/20053/16/20053/16/2005APASS
DetailsTroy Cobbley
Undergrouund supply flush was not done. Underground and attic system hydro test passed 3/16/2005 11:14:57 AM
INSP-Supply line flush3/3/20053/3/20053/3/2005APART
DetailsTroy Cobbley
Underground supply piping is ok to cover. Notified contractor that a tamper switch would be needed for the Post Indicator Valve. 3/3/2005 1:18:56 PM
FIR-Aging Inspection2/17/20052/17/20052/17/2005 NR
DetailsTroy Cobbley
Per tom work is in progress 2/17/2005 4:39:08 PM