INSP-Final Inspection | 9/2/2005 | 9/2/2005 | 9/2/2005 | P | PASS |
Forrest France
|
|
|
Defficient items have been corrected and inspected, permit finaled.
|
INSP-Sprinkler Rough-in/Hydro | 8/29/2005 | 8/29/2005 | 8/29/2005 | P | PART |
Forrest France
|
|
|
Re-hydrostatic test of the dry system passed inspection.
|
INSP-Final Inspection | 8/26/2005 | 8/26/2005 | 8/26/2005 | P | FAIL |
Forrest France
|
|
|
Exposed CPVC line in attic space needs tenting, one branch line has the deflectors oriented opposite the roof pitch, provide approved lateral restraint for all sprig-ups over 4' in length, perform a hydrostatic test due to the number of changes and additional heads installed for the correction of spacing issues in the attic.
|
INSP-Sprinkler Rough-in/Hydro | 8/18/2005 | 8/18/2005 | 8/18/2005 | P | CANC |
Troy Cobbley
|
|
|
Wrong permit called in. See FIR 05-00124
|
INSP-Sprinkler Rough-in | 8/16/2005 | 8/16/2005 | 8/16/2005 | P | FAIL |
Troy Cobbley
|
|
|
Dry system tripped ok but became plugged with something
|
INSP-Sprinkler Rough-in/Hydro | 8/11/2005 | 8/11/2005 | 8/11/2005 | P | PASS |
Troy Cobbley
|
|
|
Wet system hydro test passed
|
INSP-Sprinkler Rough-in/Hydro | 8/10/2005 | 8/10/2005 | 8/10/2005 | P | FAIL |
Troy Cobbley
|
|
|
Wet system hydro test failed again.
|
INSP-Sprinkler Rough-in | 8/9/2005 | 8/10/2005 | 8/10/2005 | A | FAIL |
Troy Cobbley
|
|
|
Dave found leak in system. Test rescheduled for this afternoon.
|
INSP-Sprinkler Rough-in/Hydro | 7/28/2005 | 7/29/2005 | 7/29/2005 | P | PASS |
Troy Cobbley
|
|
|
contact dave. finish 24 hr air; air test passed
|
INSP-Sprinkler Rough-in/Hydro | 7/27/2005 | 7/28/2005 | 7/28/2005 | P | PART |
Troy Cobbley
|
|
|
contact dave. 24 hr air test.; Starting pressure at just above 42psi at 12:00
|
INSP-Sprinkler Rough-in/Hydro | 7/27/2005 | 7/28/2005 | 7/28/2005 | A | PASS |
Troy Cobbley
|
|
|
Above ground hydro test passed.
|
INSP-Sprinkler Rough-in/Hydro | 7/27/2005 | 7/27/2005 | 7/27/2005 | P | CANC |
Troy Cobbley
|
|
|
Wrong permit called in. See FIR05-00124
|
INSP-Sprinkler Rough-in | 7/21/2005 | 7/25/2005 | 7/25/2005 | A | CANC |
Troy Cobbley
|
|
|
Canceled per Dave until resubmittals for piping changes are approved.
|
INSP-Sprinkler Rough-in | 7/20/2005 | 7/22/2005 | 7/22/2005 | P | CANC |
Troy Cobbley
|
|
|
Contact Dave Around 1 PM please.; Phone #: ###-#### Cancelled per Dave's request.
|
INSP-Sprinkler Rough-in | 5/6/2005 | 5/6/2005 | 5/6/2005 | P | PART |
Troy Cobbley
|
|
|
Sprinkler piping under mezzanine, including the ramp are ok to cover. Flexible cplg has been installed on rise up.
|
INSP-Sprinkler Rough-in | 5/4/2005 | 5/5/2005 | 5/4/2005 | A | FAIL |
Troy Cobbley
|
|
|
Inspection was for the area under the mezzanine as shown on the resubmitted plans. Plans do not show the upright heads for the combustible concealed space. There are six uprights mounted above the pendants. They are 200 degree QR brass uprights.
|
INSP-Sprinkler Rough-in/Hydro | 4/19/2005 | 4/20/2005 | 4/20/2005 | P | FAIL |
Forrest France
|
|
|
Head required in entry north side for combustible concealled space. Move 4-way brace closer to change of direction on 3'' main. Flexible coupling req. on 2.5" main through floor at mech. mezz. Verify 10' length on lateral EQ bracing is sufficient. Two
|
INSP-Supply line flush | 4/4/2005 | 4/5/2005 | 4/5/2005 | A | PASS |
Troy Cobbley
|
|
|
Undergroiund supply line flush passed
|
INSP-Sprinkler Rough-in | 3/23/2005 | 3/24/2005 | 3/24/2005 | A | PART |
Troy Cobbley
|
|
|
terry; Phone #: ###-#### Dry system east side project ok to cover. 3/24/2005 9:27:17 AM
|
INSP-Sprinkler Rough-in/Hydro | 3/24/2005 | 3/24/2005 | 3/24/2005 | A | CANC |
Troy Cobbley
|
|
|
Contact: Terry - Cover Inspection; Phone #: ###-#### Duplicate inspection. 3/24/2005 9:31:26 AM
|
INSP-Sprinkler Rough-in | 3/22/2005 | 3/23/2005 | 3/23/2005 | A | FAIL |
Troy Cobbley
|
|
|
Contact: Terry - Cover Inspection; Phone #: ###-#### See field remarks on approved plans re EQ attatchments and ssu spacing. 3/23/2005 12:01:15 PM
|