Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR04-00748
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 12551 W EXECUTIVE DR
Project NameSPR UG SHELL WAREHOUSE/OFFICE
Customer Number 
ePlanReview 
Description
RONALD VAN AUKER WAREHOUSE & OFFICE (SHELL ONLY) - Install approximately 103 LF of 6" C-900 PVC underground fire service supply, from an existing 6" tap on the south side (property line) of Executive drive, running south to approximately 4'-9" east of column #2, 1'-6" inside the footing. Piping rising up thought the floor with 6" D.I. to approximately 6" above the finished floor with an MJ X Flange Adapter. This service supply is for a new 17,000-ft/2, (16,000 square foot enclosed building shell with a 1,000 square foot roof covered storage area at the west side of the building), one story, concrete tilt-up and steel shell warehouse and office building. This permit is for the construction of the underground supply. Overhead fire sprinkler system will require separate permitting. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD04-02121.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/8/20056/8/20056/8/2005PPASS
DetailsTroy Cobbley
permit finaled
INSP-Supply line flush4/18/20054/19/20054/19/2005PPASS
DetailsForrest France
Underground fire supply line flush OK.
INSP-Supply line flush3/11/20053/14/20053/14/2005APART
DetailsTroy Cobbley
Underground hydro test passed. Rough-in failed. Trapeze hangers for the 6" main are overspace. Plans call for 10' max. Provide calcs and spacing requirements for the uni-strut tapeze on the 4" main. Provide verification for head temps at the unit heaters. Backflow preventer in wrong type of manufacturer. Head spacing and pipe size ok. Riser not looked at. 3/14/2005 11:33:22 AM
INSP-Sprinkler Rough-in/Hydro1/31/20052/1/20052/1/2005APART
DetailsRick Jackson
Please call one hour prior to arrival. Stan is the contact at ###-####. Thank you; Phone #: ###-#### Internet Inspection Request from: Trent Bice UG cover okay per resubmittals; 8 inch with tracer wire 2/1/2005 12:11:17 PM