Permit Information
Permit NumberFIR04-00761
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 5874 W STATE ST
Project NameSPR NAMPA FLOORS & INTERIORS
Customer Number 
ePlanReview 
Description
NAMPA FLOORS & INTERIORS * To install approximately 22'-0' of 6" C-900 PVC underground fire service supply main from the property line in N. Kessinger lane, west, under the footing and up through the finished floor with 6" Ductile Iron and a 6"x11" M.J. adapter to approximately 6" above the finish floor. To install a complete NFPA 13, Ordinary Group 2 hazard system in the new 8,420-ft/2, one story, wood framed retails store for flooring and interiors sales. This building contains M and S-1 occupancies and was reviewed using the unseparated uses option (IBC, Section 302.3.2). The S-1 is limited to commodity use addressed in the review comments (item #16). The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD04-01600.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/20/20055/20/20055/20/2005PPASS
DetailsTroy Cobbley
Fire sprinkler finaled
INSP-Final Inspection5/19/20055/19/20055/19/2005PFAIL
DetailsTroy Cobbley
Provide guage on supply side, provide ball drip for FDC, provide backflow certification and forward flush, provide pendants for the head box and provide wall PIV per the approved plans.
INSP-Sprinkler Rough-in/Hydro5/12/20055/13/20055/13/2005APART
DetailsTroy Cobbley
Underground and overhead hydro test passed. Underground flush passed. See approved plans for overhead piping deficiencies.
INSP-Sprinkler Rough-in2/16/20052/17/20052/17/2005APART
DetailsTroy Cobbley
Sprinkler piping over hardlid areas is ok to cover. Trapeze needs to be upsized per review notes. Underground supply piping is ok to cover. 2/17/2005 1:44:58 PM