Permit Information
Permit NumberFIR05-00029
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 5208 W IRVING ST
Project NameSPR WAREHOUSE BLD@5208 IRVING
Customer Number 
ePlanReview 
Description
WAREHOUSE BUILDING @ 5208 IRVING * To install a complete fire sprinkler system which includes the underground fire service supply and overhead piping in an existing warehouse building. This building has the height to accommodate high piled combustible storage of which fire protection meeting requirements of Boise Municipal Code 7-01-56-903.1.6. The proposed fire sprinkler design is solely for the intended tenancy of Boise City Police Department with a protection design for Ordinary Group 2 Occupancy Hazard use with warehouse limitation. Request for the reduced alternative protection is addressed in an attached letter on file from Doug Bagley, Property Manager. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is not associated to any building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/26/20071/29/20071/29/2007APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection1/9/20071/10/20071/10/2007AFAIL
DetailsTroy Cobbley
See city approved plans for items still needing completed.
INSP-Final Inspection1/2/20071/3/20071/3/2007AFAIL
DetailsTroy Cobbley
There were not approved and updated plans on site for the inspection.
INSP-Final Inspection2/13/20062/14/20062/14/2006AFAIL
DetailsTroy Cobbley
See city approved plans for deficiencies which include resubmitting plans for piping changes in the second floor storage room remote area. The riser is missing items for the final such as stickers and the backflow preventor is incorrect.
INSP-Supply line flush1/10/20061/10/20061/10/2006PPASS
DetailsTroy Cobbley
Underground supply line flush passed.
INSP-Sprinkler Rough-in/Hydro1/4/20061/5/20061/5/2006APASS
DetailsTroy Cobbley
overhead / underground hydro passed
INSP-Sprinkler Rough-in10/17/200510/17/200510/17/2005PPASS
DetailsTroy Cobbley
Underground supply line is ok to cover
INSP-Sprinkler Rough-in10/3/200510/4/200510/4/2005APART
DetailsTroy Cobbley
Office area only is ok to cover. Two upright sprinkler heads are blocked by duct work as marked on the approved plans. This will need to be fixed prior to final.