INSP-Final Inspection | 12/20/2007 | 12/21/2007 | 12/21/2007 | A | PASS |
Forrest France
|
|
|
Fire alarm permit finaled. Remainder of required building upgrade work to be completed via separate tenant permits.
|
INSP-Final Inspection | 11/26/2007 | 11/27/2007 | 11/27/2007 | A | PART |
Forrest France
|
|
|
Testing completed for notification devices at the basement, first and third floors, also completed initiating device testing including all smoke detectors, ansul kitchen system, waterflow, pull station. Final pending the installation of notification devices at floors, rooms and areas currently occupied but indicated on the plans as "unoccupied" and therefore are missing required coverage. See clouded red lines on approved set for locations at the basement, 1st, 2nd and 4th floors.
|
INSP-Conference | 11/26/2007 | 11/26/2007 | 11/26/2007 | P | DONE |
Forrest France
|
|
|
Job scheduling.
|
INSP-Final Inspection | 11/19/2007 | 11/21/2007 | 11/21/2007 | A | PART |
Forrest France
|
|
|
Tested notification devices for the 1st thru 4th floors, no access provided for some areas on the 3rd and 1st floors-will need to retest, need to remove one existing SD at the 4th floor, noted on plans devices tested today including SD's and one pull station, fire doors at some locations are not adjusted correctly for full closure, need to test remainder of initiation devices and a/v's at next inspection.
|
INSP-Final Inspection | 7/10/2006 | 7/10/2006 | 7/10/2006 | P | PART |
Forrest France
|
|
|
C/N items from the previous inspection have been verified for completion, tested main FACP batteries, AC loss, phone lines, smoke above panel, need to provide locks at breakers, tested tamper switches, flow switches, addresses at flows do not match map or actual location. SD, manual pulls and notification to be tested at next inspection request. Duct detector testing is complete.
|
INSP-Final Inspection | 6/26/2006 | 6/29/2006 | 6/29/2006 | A | FAIL |
Forrest France
|
|
|
Tested all duct detectors today, one detector(device 30) in the basement failed to function, one detector on the 2nd floor will need to be relocated as it is upstream of a return grill, need to change descriptor of one detector location at the cafe ole office area. Noted that the SD's located adjacent to the atrium in several locations will not function as installed due to open ceiling beam obstructions greater than 12" in depth.
|
FIR-Aging Inspection | 5/30/2006 | 5/30/2006 | 6/5/2006 | | DONE |
Forrest France
|
|
|
Work in progress.
|