Permit Information
Permit NumberFIR05-00068
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 12400 W MCMILLAN RD
Project NameSPR OH CENTENIAL PERFORNING
Customer Number 
ePlanReview 
Description
CENTENNIAL HIGH SCHOOL PERFORMING ARTS CENTER * To install a complete overhead fire sprinkler system with Class III, 1½" and 2½" hose connections on the each side of the stage in a new 32,606-ft/2, one story, Type II-B theater/classroom building. The underground fire service supply was installed under separate fire permit FIR04-00619 (by the same contractor). Fire sprinklers are used for area. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD04-01188.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/18/20061/19/20061/19/2006APASS
DetailsTroy Cobbley
Sprinkler permit finaled
INSP-Final Inspection12/28/200512/29/200512/29/2005PFAIL
DetailsTroy Cobbley
Need to do all of the riser inspection including the forward flush. Provide E.Q. on the three sprig ups. Provide the correct connections for the stage hose valves. There is a clearance issue in the storage room. Check ball drip.
INSP-Final Inspection10/19/200510/20/200510/20/2005PFAIL
DetailsTroy Cobbley
Project is not ready for final. Need the latest and greatest plans, canopies missing, taped heads...ect.
INSP-Sprinkler Rough-in/Hydro10/19/200510/20/200510/20/2005PPASS
DetailsTroy Cobbley
Above ground hydro test passed
INSP-Sprinkler Rough-in/Hydro7/21/20057/21/20057/21/2005PPART
DetailsTroy Cobbley
Hanger dificiencies as marked on the last edition of the approved have been corrected but the latest revision of the plans was not on site.
INSP-Sprinkler Rough-in5/19/20055/20/20055/20/2005APART
DetailsTroy Cobbley
Sprinkler piping fo rthe most part is ok. See city approved plans for locations of deficiecies which include missing hangers, modified routing of piping, deletion of heads and additional heads to be required under duct work in the auditorium. Plans will n
INSP-Sprinkler Rough-in5/3/20055/3/20055/3/2005PPART
DetailsTroy Cobbley
Sprinkler piping for room 137 is ok to cover. Looked at the eq bracing for the north half of building. It looks ok.