Permit Information
Permit NumberFIR05-00075
StatusFinaled
Name SYNERGY ENGINEERS
Site Address 850 W BROAD ST
Project NameBODO BLDG #4 - ALM
Customer Number 
ePlanReview 
Description
To provide a required manual fire alarm system (building is slated for A2, B and M occupancies). The required manual fire alarm system includes sprinkler monitoring, elevator recall/shutdown and notification throughout.

The associated building permit (BLD 04-01255) is to construct a new 52,260 Square foot, two story, noncombustible, fully fire sprinklered shell and core building for future office, retail and restaurant tenants. This work also includes the construction of a two-hour fire-resistive, noncombustible, four story stair enclosure to used as the second exit from the new building and the existing four story Foster Building. This new building will wrap around the existing Foster Building and 9th Street Parking Garage. There will be no property lines through or between any of the building on this block. Two-hour fire walls will separate these buildings from each other, because of allowable area and construction types. The new building is being constructed with non separated uses with the A-2 Occupancy being the most restrictive. The fire sprinkler system is being used for area increase. This is a shell and core permit only and no occupancy is allowed under this permit. Separate tenant improvement permit are required to finish this building for occupancy. All construction per the approved plans and attached comment list. #04-385/JCM BoDo - Building #4 (Shell & Core) -
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/20/20064/21/20064/21/2006APASS
DetailsForrest France
Final fire alarm inspection passed, permit finaled.
INSP-Final Inspection4/20/20064/20/20064/20/2006PFAIL
DetailsForrest France
The outside bell failed to operate upon water flow, elevator lobby smokes tested okay, tampers at the basement and 1st floor tested okay.
INSP-Final Inspection4/18/20064/19/20064/20/2006PDEFR
DetailsForrest France
Scheduled by a contractor via Hello! on 4/18/2006 at 3:35:00 PM. Contact: ###-####.
INSP-Final Inspection4/13/20064/14/20064/14/2006ANR
DetailsForrest France
Project not ready for inspection due to related fire sprinkler issues and a non-functional elevator.
INSP-Final Inspection2/27/20062/28/20062/28/2006APASS
DetailsForrest France
c/n items have been completed, fire alarm permit for BODO #4 has beeen completed.
INSP-Alarm Testing11/22/200511/23/200511/22/2005PCANC
DetailsForrest France
Scheduled by a contractor via Hello! on 11/22/2005 at 2:37:38 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Nov 22 2005 2:39PM.
INSP-Alarm Testing10/27/200510/28/200510/28/2005APART
DetailsForrest France
A temporary approval was signed with Sam Rogers permission pending resubmittals for changed EOL, west elevator completion, permanent signage at the FACP room door.
INSP-Sprinkler Rough-in10/27/200510/28/200510/28/2005ACANC
DetailsForrest France
brian ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
INSP-Alarm Testing10/24/200510/25/200510/25/2005AFAIL
DetailsForrest France
Provide audibility in the FACP room, provide signage at door to FACP room, provide resubmittals for EOL changes and added horn for FACP room, west elevator is not complete yet, provide Knox box with key and map, Foster bld. monitoring and elevator controls are incomplete.
INSP-Alarm Testing10/24/200510/24/200510/24/2005AFAIL
DetailsForrest France
Need to retest elevator lobby smoke detectors as they have been connected and reconnected for ceiling tile installation, need to test elevator heat detector in pit, provide sign at FACP room, no knox box provided yet, need audibility in the FACP room as discussed.
INSP-Alarm Testing10/18/200510/21/200510/21/2005AFAIL
DetailsForrest France
Heat detector in the north elevator pit is too far from the sprinkler head, provide resubmittals for the EOL 2nd floor, tape on strobe and no ceiling tile 1st floor north, west elevator is not complete, provide sign at the door to FACP room, provide audible notification for the electrical room and FACP, provide knox box.
INSP-Alarm Testing10/20/200510/20/200510/20/2005PFAIL
DetailsForrest France
PIV tamper failed to function properly, the north elevator failed to recall upon smoke detection, the west elevator is not completed to allow testing, elevator control voltage needs to be monitored as a supervisory not a trouble signal, provide a sign at the door to the FACP, testing not completed today due to time constraints.