Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR05-00076
StatusFinaled
Name SYNERGY ENGINEERS
Site Address 301 S CAPITOL BLVD
Project NameBODO BUILDING 7 ALARM
Customer Number 
ePlanReview 
Description
To provide a required manual fire alarm system (building is slated for A1, A2, B and M occupancies). The required manual fire alarm system includes sprinkler monitoring, elevator recall/shutdown and notification throughout.

The associated building permit (BLD 04-01324) is to construct a new 135,950 square foot, three story, noncombustible, fully fire sprinklered shell building for future multi-plex theater, offices, retail and restaurant tenants. The new building is being constructed with non separated uses with the A-1 Occupancy being the most restrictive. The fire sprinkler system is being used for area increase. This is a shell permit only and no occupancy is allowed under this permit. Separate tenant improvement permit are required to finish this building for occupancy. All construction per the approved plans and attached comment list. #04-386/JCM BoDo - Building #7 (Shell) -
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/10/20063/13/20063/13/2006APASS
DetailsForrest France
Required items on the correction notice have been completed, shell and core fire alarm permit finaled.
INSP-Final Inspection2/27/20062/28/20062/28/2006PFAIL
DetailsForrest France
Need to post building map showing roof plan including clock tower, update plans and 1st floor map to show changed EOL location from device 8:8.
INSP-Alarm Testing11/22/200511/23/200511/23/2005PPART
DetailsForrest France
The north elevator alarm devices tested okay.
INSP-Alarm Testing11/22/200511/22/200511/22/2005PCANC
DetailsForrest France
INSP-Final Inspection11/10/200511/10/200511/10/2005PPART
DetailsTroy Cobbley
A temporary occupancy was given with Dave Hanniman's permission until resubmittals and elevator are finished and finaled. Elevator is not to be used until inspected.
INSP-Alarm Testing11/9/200511/9/200511/9/2005PPART
DetailsForrest France
The north elevator remains to be completed and tested, final pending verification of resubmittals for field changes.
INSP-Sprinkler Rough-in10/27/200510/28/200510/28/2005APART
DetailsForrest France
North elevator is still non-functional, provide resubmittals for all required changes.
INSP-Alarm Testing10/24/200510/25/200510/25/2005PFAIL
DetailsForrest France
North elevator is not functional at this time, need an additional SD above the FACP due to a beam pocket obstruction, clock tower AV is not functional, provide signage at FACP room door, outside bell to be relocated at face of brick, elevator roof damper is not required due to barometric shaft, resubmitt for changed EOL, added devices, deleted damper and revised matrix for pump, provide audibility for the FACP room.
INSP-Alarm Testing10/24/200510/24/200510/24/2005APART
DetailsForrest France
Partial shell alarm inspection only.
INSP-Alarm Testing10/21/200510/21/200510/21/2005PFAIL
DetailsForrest France
Lower pull station to 48" AFF, provide additional smoke at the panel due to beam blockage, verify audibility in the FACP room, fire pump run shows as an alarm and the matrix indicates a supervisory, change label at roof tamper and stair flow 108, outside bell shall silence upon waterflow ceasation, all sprinkler alarms tested today, no other items tested at this time.