INSP-Final Inspection | 4/12/2006 | 4/13/2006 | 4/13/2006 | A | PASS |
Troy Cobbley
|
|
|
Fire alarm permit finaled
|
INSP-Final Inspection | 1/20/2006 | 1/20/2006 | 1/20/2006 | P | PART |
Forrest France
|
|
|
The correct back boxes have been installed in the pool area, the elevator has been state inspected and approved. Per S. Rogers a temp. occupancy was given pending field inspection of approved resubmitted plans and verification the correct sample tubes have been installed in the duct detectors.
|
INSP-Alarm Testing | 1/19/2006 | 1/19/2006 | 1/19/2006 | P | FAIL |
Troy Cobbley
|
|
|
Need to install weather proof backboxes in the pool area and provide correct sample tubes lenghts in the duct smoke detectors. Still waiting on approved resubmitted plans for the fire alarm. Per Sam Rogers a temporary occupancy can be given if the elevators get signed off by the state elevator inspectors.
|
INSP-Alarm Testing | 1/18/2006 | 1/18/2006 | 1/18/2006 | P | FAIL |
Troy Cobbley
|
|
|
Strobes do not sync, duct detectors are mounted incorrectly, need verification of weatherproof devices in the pool area, missing door hold open on first floor north stair door and a/v's are not within 15' of the ends of the corridor on the first floor on both sides of the lobby
|
INSP-Alarm Testing | 1/13/2006 | 1/13/2006 | 1/13/2006 | A | PASS |
Troy Cobbley
|
|
|
Elevator recall passed. First floor smoke detectors passed.
|
INSP-Alarm Testing | 1/12/2006 | 1/12/2006 | 1/12/2006 | P | PASS |
Troy Cobbley
|
|
|
2nd floor testing passed.
|
INSP-Alarm Testing | 1/11/2006 | 1/11/2006 | 1/11/2006 | A | DONE |
Troy Cobbley
|
|
|
Dry system, fourth and third floors have passed. Matt is to change the programming for the dampers to only reset when the panel is reset and not on silence.
|
INSP-Alarm Testing | 1/10/2006 | 1/10/2006 | 1/10/2006 | A | PART |
Troy Cobbley
|
|
|
Today we tested the fire alarm panel itself and the interconnections between it and the NAC panels. We also tested were the smoke detectors over the panels. Also tested was the wet system tamper switches and flow switches for all floors. I found one duct smoke detector that needs relocated and the north fourth floor manual pull did not work.
|
INSP-Alarm Testing | 1/9/2006 | 1/9/2006 | 1/9/2006 | P | CANC |
Troy Cobbley
|
|
|
Contractor has not lowered the manual pull stations that are mounted too high. No test performed.
|
FIR-Aging Inspection | 6/17/2005 | 6/17/2005 | 6/17/2005 | | NR |
Forrest France
|
|
|
Permit has been recently issued, work is ongoing.
|