Permit Information
Permit NumberFIR05-00104
StatusFinaled
Name E2CO
Site Address 1426 S ENTERTAINMENT AVE
Project NameOxford Suites Hotel
Customer Number 
ePlanReview 
Description
To provide a required manual fire alarm system that includes sprinkler monitoring, required automatic detection, elevator recall/shutdown, HVAC shutdown, fire/smoke damper control, door release, cooking hood monitoring and notification throughout.

4/4/2006 - See comments #24, 30 and 31.

The associated building permit (BLD 04-00640) is to construct a new 91,785 sq.ft. four story, with a basement, 132 room suite hotel. The basement is 17,287 sq.ft. and contains, conference rooms, lounge, full service restaurant with kitchen. The first floor is 21,164 sq.ft. contains the indoor swimming pool, spa, lobby area and 30 guest room. The second floor is 20.084 sq.ft. contains 32 suites the third floor is 21,164 sq.ft. contains 39 suites and the forth floor is 17,287 sq.ft. contains 31 suites. NOTE: This building is fully fire sprinklered for area increase. Separate permits are required to be obtained for the indoor pool and spa. All construction per the approved plans and attached comment list. Refer to BLD 04-01157 for Grading Permit. MJP DRH03-00148 CUP03-00068 PC#161-04 Oxford Suites Hotel *
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/12/20064/13/20064/13/2006APASS
DetailsTroy Cobbley
Fire alarm permit finaled
INSP-Final Inspection1/20/20061/20/20061/20/2006PPART
DetailsForrest France
The correct back boxes have been installed in the pool area, the elevator has been state inspected and approved. Per S. Rogers a temp. occupancy was given pending field inspection of approved resubmitted plans and verification the correct sample tubes have been installed in the duct detectors.
INSP-Alarm Testing1/19/20061/19/20061/19/2006PFAIL
DetailsTroy Cobbley
Need to install weather proof backboxes in the pool area and provide correct sample tubes lenghts in the duct smoke detectors. Still waiting on approved resubmitted plans for the fire alarm. Per Sam Rogers a temporary occupancy can be given if the elevators get signed off by the state elevator inspectors.
INSP-Alarm Testing1/18/20061/18/20061/18/2006PFAIL
DetailsTroy Cobbley
Strobes do not sync, duct detectors are mounted incorrectly, need verification of weatherproof devices in the pool area, missing door hold open on first floor north stair door and a/v's are not within 15' of the ends of the corridor on the first floor on both sides of the lobby
INSP-Alarm Testing1/13/20061/13/20061/13/2006APASS
DetailsTroy Cobbley
Elevator recall passed. First floor smoke detectors passed.
INSP-Alarm Testing1/12/20061/12/20061/12/2006PPASS
DetailsTroy Cobbley
2nd floor testing passed.
INSP-Alarm Testing1/11/20061/11/20061/11/2006ADONE
DetailsTroy Cobbley
Dry system, fourth and third floors have passed. Matt is to change the programming for the dampers to only reset when the panel is reset and not on silence.
INSP-Alarm Testing1/10/20061/10/20061/10/2006APART
DetailsTroy Cobbley
Today we tested the fire alarm panel itself and the interconnections between it and the NAC panels. We also tested were the smoke detectors over the panels. Also tested was the wet system tamper switches and flow switches for all floors. I found one duct smoke detector that needs relocated and the north fourth floor manual pull did not work.
INSP-Alarm Testing1/9/20061/9/20061/9/2006PCANC
DetailsTroy Cobbley
Contractor has not lowered the manual pull stations that are mounted too high. No test performed.
FIR-Aging Inspection6/17/20056/17/20056/17/2005 NR
DetailsForrest France
Permit has been recently issued, work is ongoing.