Permit Information
Permit NumberFIR05-00109
StatusFinaled
Name ADT SECURITY SERVICES INC
Site Address 11095 W EXECUTIVE DR
Project Namealm - Action Couriers
Customer Number 
ePlanReview 
Description
To provide a voluntary manual fire alarm system. The manual fire alarm system includes HVAC shutdown, total area detection and notification throughout (the offices for BMC Sales and Metro Movers were defined as less than 3 per space, so there is no notification in four spaces). The FACP is a combination system, the security is already installed, no access control, monitoring only. The fire signals shall have precedence over any security signal, the PDS Fire Inspector shall field verify.

4/28/2005 - Revised design, the FACP only allows smoke detectors to be installed on zones 1 and 2. The plan modification indicates the corrected zones.

Note to Inspector: This system shall comply with NFPA 72; 6.8.4.6, "In combination systems, fire alarm signals shall be distinctive, clearly recognizable, and take precedence over any other signal even when a non-fire alarm signal is initiated first.

There is no associated building permit.

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/30/20113/31/20113/31/2011APASS
DetailsTroy Cobbley
Permit finaled
FIR-Aging Inspection2/4/20112/4/20112/9/2011 NR
DetailsTroy Cobbley
I deferred this project to Jerry McAdams for follow up.
INSP-Conference7/7/20107/7/20107/7/2010PDONE
DetailsTroy Cobbley
I went over the outstanding issues as per the permit history with Keith at ADT.
INSP-Conference6/15/20106/29/20107/2/2010ADONE
DetailsTroy Cobbley
I left a message on mikes voice mail requesting job status.
FIR-Aging Inspection6/11/20106/11/20106/15/2010 NR
DetailsTroy Cobbley
I spoke to Mike with Action Couriers about getting this inspection completed. He wanted to know if Northwest Security could complete this permit instead of ADT. I let him know that a separate permit would be required if another company completed the work. He was going to follow up with ADT. A follow up conference has been set up.
INSP-Final Inspection5/11/20055/12/20055/12/2005AFAIL
DetailsTroy Cobbley
The zone #1 smoke detectors located in the storage room are not connected to the fire alarm system. Provide knox key box per review comments. Provide faxed verification of the signals.
INSP-Conference7/2/20107/7/2010 A 
DetailsTroy Cobbley
Follow up conference with Mike; ###-####