Permit Number | FIR05-00109 |
Status | Finaled |
Name |
ADT SECURITY SERVICES INC
|
Site Address |
11095 W EXECUTIVE DR
|
Project Name | alm - Action Couriers |
Customer Number | |
ePlanReview | |
Description |
To provide a voluntary manual fire alarm system. The manual fire alarm system includes HVAC shutdown, total area detection and notification throughout (the offices for BMC Sales and Metro Movers were defined as less than 3 per space, so there is no notification in four spaces). The FACP is a combination system, the security is already installed, no access control, monitoring only. The fire signals shall have precedence over any security signal, the PDS Fire Inspector shall field verify.
4/28/2005 - Revised design, the FACP only allows smoke detectors to be installed on zones 1 and 2. The plan modification indicates the corrected zones.
Note to Inspector: This system shall comply with NFPA 72; 6.8.4.6, "In combination systems, fire alarm signals shall be distinctive, clearly recognizable, and take precedence over any other signal even when a non-fire alarm signal is initiated first.
There is no associated building permit.
|