INSP-Final Inspection | 7/25/2005 | 7/25/2005 | 7/25/2005 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled, sufficient flow has been verified through the system backflow preventer.
|
INSP-Final Inspection | 7/21/2005 | 7/22/2005 | 7/22/2005 | A | FAIL |
Forrest France
|
|
|
Foreward flow test failed to produce required gpm.
|
INSP-Final Inspection | 7/19/2005 | 7/21/2005 | 7/21/2005 | A | FAIL |
Forrest France
|
|
|
Provide foreward flow test of backflow preventer, provide NFPA25, attatch calc. sticker, install missing escutcheon at riser room, sinage to indicate areas controled by system control valves.
|
INSP-Sprinkler Rough-in/Hydro | 7/5/2005 | 7/6/2005 | 7/6/2005 | A | FAIL |
Forrest France
|
|
|
Need lateral EQ brace installed on the last piece of main 2nd floor SW side per NFPA 13 9.3.5.3.4, attatch retaining straps in two locations 2nd floor, missing hangers on penthouse branch line supply, provide guages at floor control manifolds as shown on approved plans.
|
INSP-Final Inspection | 7/6/2005 | 7/6/2005 | 7/6/2005 | P | PART |
Forrest France
|
|
|
Overhead hydrostatic test of 2nd and 3rd floor shell pipe passed.
|
INSP-Sprinkler Rough-in/Hydro | 6/30/2005 | 7/5/2005 | 7/5/2005 | A | CANC |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 6/30/2005 at 3:34:44 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jul 5 2005 7:10AM.
|
INSP-Sprinkler Rough-in/Hydro | 6/21/2005 | 6/23/2005 | 6/23/2005 | A | FAIL |
Forrest France
|
|
|
Shell area first floor needs hanger at 1" arm over, head cage in elevator pit, SW is blocked in electrical room, inadequate coverage at bottom stair landings. 2nd and 3rd floor shell piping not ready for inspection.
|
INSP-Sprinkler Rough-in/Hydro | 6/23/2005 | 6/23/2005 | 6/23/2005 | P | PART |
Forrest France
|
|
|
Standpipe and overhead hydro test of first floor piping OK.
|