Permit NumberFIR05-00121
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 12450 W EXECUTIVE DR
Project NameSPR MIDWEST FLOOR COVERING
Customer Number 
ePlanReview 
Description
(MIDWEST FLOOR COVERING)(VAN AUKER CLOVERDALE #10 BLDG) To install a complete overhead fire protection (sprinkler) system in a new 26,400-ft/2 shell building with a new tenant to occupy the entire warehouse with a new 1,660-ft/2 accessory office area with a (light) storage mezzanine (above) and a small 144-ft/2 H-3 occupancy flammable liquid storage room. The fire sprinkler work is related to the new shell constructed under BLD03-01306, the new tenant mezzanine with stairway, with two new offices and restrooms, with a breakroom beneath all with suspended ceilings, a new H-3 occupancy flammable liquids storage room along with racking in the warehouse (to be constructed under a separate building permit). This building is fully fire sprinklered. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The shell building permit was BLD03-01306. Fire underground fire service supply was installed under FIR04-00643. This associated overhead fire sprinkler work permit is attached to building permit: BLD04-02971.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/20/20054/21/20054/21/2005APASS
DetailsForrest France
Overhead fire sprinkler rough-in pass. Flow req. verified. Additional rack sprinklers on separate permit not installed.
INSP-Final Inspection4/19/20054/20/20054/20/2005PFAIL
DetailsTroy Cobbley
Could not get the required pressure to pass forward flush test. Still need to verify sprinkler spacing as noted on previous inspection
INSP-Sprinkler Rough-in/Hydro4/18/20054/18/20054/18/2005PFAIL
DetailsTroy Cobbley
Multiple branchlines have been relocated and now appear to exceed 99 sq.ft. max. spacing. Provide verification that afcon 303 rings have been used for the trapeze hangers. Provide flexible cplings at the top and bottom of the risers at the inracks. Provid
INSP-Conference4/15/20054/18/20054/18/2005AFAIL
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 4/15/2005 at 2:18:57 PM. Contact: ###-####. No body at the site for the conference. I called Treasure Valley's office prior to showing up but the lady who answered the phone wasn't sure who I needed to talk
INSP-Sprinkler Rough-in/Hydro4/13/20054/14/20054/14/2005APASS
DetailsForrest France
Overhead hydro. test passed. Rough-in OK for TI office space only.
INSP-Sprinkler Rough-in/Hydro4/11/20054/12/20054/12/2005AFAIL
DetailsForrest France
Hydro. AG not ready for test, Rough in fail; need proper temp. heads in storage room, Upright in break room is too far below deck, Upright heads in office and open office are blocked by ductwork in some locations.