INSP-Final Inspection | 8/29/2005 | 8/30/2005 | 9/2/2005 | A | PASS |
Forrest France
|
|
|
Attic spacing issues have been corrected and inspected, permit finaled.
|
INSP-Final Inspection | 8/18/2005 | 8/18/2005 | 8/18/2005 | P | FAIL |
Troy Cobbley
|
|
|
Maximum head spacing for the attic heads is 120sq. ft. per review note #9. The uprights are overspaced in many locations off the walls in the attic. Upright sprinklers are not sloped with roof deck at the southend of the attic. CPVC piping is not tented correctly in the attic at the central area. Verify that the cpvc piping exposed in the mechanical room can be. Remove switch at the air compressor.
|
INSP-Sprinkler Rough-in/Hydro | 8/8/2005 | 8/9/2005 | 8/9/2005 | A | PASS |
Troy Cobbley
|
|
|
Eq bracing on the cpvc main is done and the pendant heads are now correct. Need to inspect the dry system and hydro test the wet system and all other final items.
|
INSP-Sprinkler Rough-in/Hydro | 7/28/2005 | 7/29/2005 | 7/29/2005 | P | PASS |
Troy Cobbley
|
|
|
contact dave. finish 24 hr air.; Air test passed
|
INSP-Sprinkler Rough-in/Hydro | 7/27/2005 | 7/28/2005 | 7/28/2005 | P | PART |
Troy Cobbley
|
|
|
contact dave. 24 hr air test.; Starting pressure at just above 43psi at 12:00
|
INSP-Sprinkler Rough-in/Hydro | 7/27/2005 | 7/27/2005 | 7/27/2005 | P | PASS |
Troy Cobbley
|
|
|
Dry system hydro tested passed
|
INSP-Sprinkler Rough-in/Hydro | 7/27/2005 | 7/27/2005 | 7/27/2005 | P | FAIL |
Troy Cobbley
|
|
|
Inspection was for the cpvc piping in the existing areas. Wrong pendants installed. Will need to verify esch. for pendants. Need to provide eq. bracing for the cpvc mains
|
INSP-Conference | 7/14/2005 | 7/14/2005 | 7/14/2005 | P | DONE |
Troy Cobbley
|
|
|
I spoke to Dave with Debest about possible rated walls in the existing school. I referred him back to the architect. I also noted exposed wood including beams and 2x4's located above the ceiling that have no sprinkler protection.
|
FIR-Aging Inspection | 6/15/2005 | 6/15/2005 | 6/15/2005 | | DONE |
Troy Cobbley
|
|
|
Work in progress
|