Permit Number | FIR05-00128 |
Status | Finaled |
Name |
HONEYWELL INC
|
Site Address |
190 E BANNOCK ST
|
Project Name | ALM - ST LUKES |
Customer Number | GROUND FLOOR |
ePlanReview | |
Description |
To install a new FACP (18) and relocate one NAC extender panel from the ground floor to the basement (communication room) to prepare for a large remodel that is associated with BLD04-02203. The new FACP will monitor two existing SLC loops (SLC-01 sub-basement; from FACP-02-SLC-0-1 and SLC-02, east mechanical basement, from FACP-06-SLC-01). The NAC panel is being relocated ~ 10 feet down one floor to the same space. The same notification circuits will be extended and re-connected. (NAC-1, NAC-8, NAC-9 and NAC-10 all located in the sub-basement). There are no plans with this permit, just a riser diagram. The building maps will be furnished at the time of inspection to afford locations of the affected circuits. The PDS Fire Inspector shall field verify functionality of the SLCs and the extended NAC circuits. No written comments. The battery and voltage drop calculations appear adequate.
There is no associated building permit.
|