Name PROTEX
Site Address 500 W BROAD ST
Project Namealm -500 BROAD STREET BLDG
Customer Number 
ePlanReview 
Description
To provide security door release upon fire alarm signal. The existing required sprinkler monitoring fire alarm system includes HVAC shutdown. The plans indicate the four (4) main entrance doors (two (2) north and two (2) south) have outfitted with access controlled egress. These doors must comply with the functionality as required in the IFC 1003.3.1.3.4. The battery calculation appears to have sufficient capacity. No written comments, PDS Fire Inspector to field verify proper functionality of the releasing of the security mag locks. An updated building map shall be provided at time of inspection.

There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/19/20054/19/20054/19/2005PPASS
DetailsForrest France
Fire alarm finaled. Mag door locks operated properly under test conditions.
INSP-Final Inspection4/15/20054/18/20054/18/2005APASS
DetailsForrest France
Life safety finaled. Mag door locks operated properly under test conditions.