ePlanReview | |
Description |
To provide security door release upon fire alarm signal. The existing required sprinkler monitoring fire alarm system includes HVAC shutdown. The plans indicate the four (4) main entrance doors (two (2) north and two (2) south) have outfitted with access controlled egress. These doors must comply with the functionality as required in the IFC 1003.3.1.3.4. The battery calculation appears to have sufficient capacity. No written comments, PDS Fire Inspector to field verify proper functionality of the releasing of the security mag locks. An updated building map shall be provided at time of inspection.
There is no associated building permit.
|