Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR05-00154
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 2980 S WISE WAY
Project NameSPR BLEDSOE GROUP
Customer Number 
ePlanReview 
Description
BLEDSOE GROUP * This is limited scope of work fire permit. To remove and upgrade the fire sprinkler system protection in the Prep and Spray paint room. Also to install sprinklers (6) under existing overhead doors and add tamper switches to two existing antifreeze system control valves. Other work related in the building permit, but not addressed in this fire protection permit is "remodel an existing cabinet shop by upgrading requirements to the dust collection system. This building is fully fire sprinklered for area. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-02877.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/23/20055/24/20055/24/2005PPASS
DetailsForrest France
Fire sprinkler finaled.
INSP-Sprinkler Rough-in/Hydro5/24/20055/24/20055/24/2005PPASS
DetailsForrest France
Overhead hydrostatic test of spray room supply and branch lines passed inspection.
INSP-Final Inspection5/20/20055/23/20055/23/2005PFAIL
DetailsForrest France
Pendent heads in hallway need to match response rating per NFPA 13 8.3.3.2. Upright heads above spray room are overspaced, need to meet 130 sq foot req. Perform hydrostatic test per. review notes.
INSP-Final Inspection5/3/20055/4/20055/4/2005ACANC
DetailsForrest France
Cancel inspection per general contractor, not ready..
INSP-Final Inspection5/2/20055/3/20055/3/2005PCANC
DetailsTroy Cobbley
harry; Phone #: ###-#### Ran out of time to do inspection.
INSP-Sprinkler Rough-in4/18/20054/18/20054/18/2005PFAIL
DetailsForrest France
Fail inspection, fire sprinkler changes in spray booth and exterior compressor room not completed.
INSP-Final Inspection4/14/20054/15/20054/15/2005AFAIL
DetailsForrest France
Re-submitted approved plans and notes not available for review. Job supervisor seeks temp. occupancy approval.