Permit NumberFIR05-00183
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 6910 W STATE ST
Project NameSPR ID STATE LIQUOR STORE
Customer Number 
ePlanReview 
Description
IDAHO STATE LIQUOR STORE * To relocate 34 existing fire sprinklers for the remodel an existing 3,144-ft/2 tenant space, which is adding 180-ft/2 for a total 3,324-ft/2. The fire sprinkler work is related to some selective demolition of interior partitions, the construction of new partitions to create two new restrooms and a demising wall, the installation of a new suspended ceiling system with lighting. New insulation is being installed at the roof, requiring 32 Upright sprinklers being adjusted also. No other relocating shown or addressed above ceiling combustible cavity protection. No additional fire sprinkler work addressed for west of the new tenant demising wall. This building is fully fire sprinklered. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-00367.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/22/20054/22/20054/22/2005PPASS
DetailsTroy Cobbley
fire sprinkler finaled
INSP-Sprinkler Rough-in4/18/20054/19/20054/19/2005APART
DetailsTroy Cobbley
Sprinkler pipe in 6910 is ok to cover. Will need to verify that two existing eq braces on sprig ups have been re-installed. Upright heads need to be added along the 6914 side of the 6910/6914 separation wall since they are overspaced.
INSP-Sprinkler Rough-in4/15/20054/18/20054/18/2005AFAIL
DetailsTroy Cobbley
###-#### No responce from Grinnell when I called and can not find approved sprinkler plans at job site