INSP-Final Inspection | 1/24/2006 | 1/25/2006 | 1/25/2006 | A | PASS |
Forrest France
|
|
|
Fire sprinkler work completed satisfactory, permit finaled.
|
INSP-Sprinkler Rough-in/Hydro | 1/3/2006 | 1/3/2006 | 1/3/2006 | P | PART |
Forrest France
|
|
|
Overhead rough-in at area as marked on approved plan is acceptable, escutcheons at hard lid ceilings are missing, a 2" threaded tee is leaking- location marked on plans.
|
INSP-Sprinkler Rough-in/Hydro | 12/19/2005 | 12/19/2005 | 12/19/2005 | P | PART |
Forrest France
|
|
|
Overhead rough-in is good for cover at four hard lid areas as marked on approved plans.
|
INSP-Sprinkler Rough-in/Hydro | 12/9/2005 | 12/9/2005 | 12/9/2005 | P | PART |
Forrest France
|
|
|
Overhead rough-in at the mens locker room and rooms adjacent to the elevator as marked on approved plans are acceptable to cover.
|
INSP-Sprinkler Rough-in | 12/1/2005 | 12/2/2005 | 12/2/2005 | A | PART |
Forrest France
|
|
|
Specials lab main and one head in hard lid area are good for cover.
|
INSP-Sprinkler Rough-in/Hydro | 11/15/2005 | 11/15/2005 | 11/15/2005 | P | PART |
Forrest France
|
|
|
Overhead rough-in in two separate corridor locations as circled on approved plans are good for cover.
|
INSP-Sprinkler Rough-in/Hydro | 10/20/2005 | 10/21/2005 | 10/21/2005 | A | FAIL |
Troy Cobbley
|
|
|
The sprinkler piping doesn't match installation for the Special Services area. Contractor needs to resubmit plans that match installation. A 1 1/2" loop has been installed and 1 1/4" branchline is being used to supply new pendants that is not shown on the plans.
|
INSP-Sprinkler Rough-in/Hydro | 10/6/2005 | 10/6/2005 | 10/6/2005 | P | PART |
Forrest France
|
|
|
Overhead piping inspected for cover at soffits in the specials lab.
|
INSP-Sprinkler Rough-in | 9/15/2005 | 9/16/2005 | 9/16/2005 | A | PART |
Forrest France
|
|
|
Overhead rough-in for system 10 west side sheet FP1 is acceptable to cover.
|
INSP-Sprinkler Rough-in/Hydro | 9/15/2005 | 9/15/2005 | 9/15/2005 | P | CANC |
Forrest France
|
|
|
No time for this inspection today, have rescheduled with contractor for friday am 9/16.
|
INSP-Sprinkler Rough-in/Hydro | 8/3/2005 | 8/3/2005 | 8/3/2005 | P | FAIL |
Forrest France
|
|
|
One hanger is missing on an arm over for the pendent head in the H/K closet. Three other hard lid areas as marked on the approved plans are okay to cover.
|
INSP-Conference | 7/28/2005 | 7/28/2005 | 7/28/2005 | P | CANC |
Forrest France
|
|
|
Inspection is re-scheduled for tomorrow a.m per Phil Doble.
|
INSP-Final Inspection | 6/28/2005 | 6/28/2005 | 6/28/2005 | A | PART |
Troy Cobbley
|
|
|
Early Completion area "C" passed. Heads corrected in GS202 and GS203. Inspected two additional pendant heads which have been circled and dated on city approved plans.
|
INSP-Final Inspection | 6/27/2005 | 6/27/2005 | 6/27/2005 | P | CANC |
Forrest France
|
|
|
Cancel inspection per Phil Doble, not ready for inspection today.
|
INSP-Sprinkler Rough-in/Hydro | 6/20/2005 | 6/20/2005 | 6/20/2005 | P | FAIL |
Forrest France
|
|
|
Pendent heads are blocked by proximity to columns in womens lockers GS202, two heads are supplied by a 1" feed in womens GS203- see note #12 on plan review comments for requirements. Heads circled in red on approved plans are the only areas inspected at this time.
|