Permit Information
Permit NumberFIR05-00236
StatusFinaled
Name HONEYWELL INC
Site Address 190 E BANNOCK ST
Project Namealm - SLRMC - gnd flr imaging
Customer Number 
ePlanReview 
Description
To provide required automatic detection, manual fire boxes, HVAC shutdown (existing duct detectors are being replaced), fire/smoke damper control, door release and notification throughout the remodeled area on the ground level. The existing fire alarm system includes sprinkler monitoring, required automatic detection, HVAC shutdown, fire/smoke damper control, door release, elevator recall/shutdown and notification throughout (high rise).

6/21/2005 - A temporary office has been shown at column lines Q/19. A strobe will be installed for total coverage.

9/15/2005- Plan Modification. Fire alarm plans have changed based upon the architectural changes.

East plan includes six (6) additional strobes, two smoke detectors and a single heat detector. The mods are clouded and shown as REVC on FACP-02 Riser.

West plan includes two (2) additional strobes. The mods are clouded and shown as REVB on FACP-08 Riser.

10/20/2005- Plan Modification. Fire alarm plans have changed based upon the architectural changes.

East plan includes two (2) additional strobes and two (2) smoke detectors. The mods are clouded and shown as REVD on FACP-02 Riser. The rooms involved are Vending GC005C and Consult GC005B.

The associated building permit (BLD 04-02203) is to remodel 26,150 sq.ft. of existing areas currently used as surgery support space for medical imaging per approved plans. Work includes selective demolition; new interior, non-combustible, fire-resistive walls to create exam, treatment, recovery and support areas; a 1-hour fire barrier to create a medical imaging suite; corridor walls to form a barrier against smoke; 1-hour walls at incidental use area storage rooms as indicated; electrical, mechanical, plumbing, medical gases, sprinkler and alarm systems upgrades to meet tenant needs and comply with minimum code. PC04-622/drs. ST LUKES-S & CENTRAL WING-GROUND FLOOR & SUB BASEMENT)(MEDICAL IMAGING)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/4/20061/5/20061/5/2006APASS
DetailsForrest France
The remaining portions of the alarm permitted work passed final inspection.
INSP-Final Inspection12/21/200512/22/200512/22/2005APASS
DetailsForrest France
Defficient issues have been corrected, inspection passed.
INSP-Final Inspection12/20/200512/21/200512/21/2005AFAIL
DetailsForrest France
Strobe in the staff break room is blocked by a wall not shown on plans, coverage in this area is incomplete, relocate or add an additional device, all other items tested okay.
INSP-Sprinkler Rough-in/Hydro9/26/20059/27/20059/27/2005PPASS
DetailsForrest France
Items on correction notice have been completed, fire alarm passed inspection.
INSP-Final Inspection9/23/20059/26/20059/26/2005AFAIL
DetailsForrest France
SD is overspaced in file room, SD in two adjacent rooms as marked on plans are too close to HVAC diffusers, one strobe in restroom with drop ceiling is mounted too high, all other items tested okay, provide latest resubmittals at next inspection.
INSP-Alarm Testing6/22/20056/23/20056/23/2005APART
DetailsForrest France
Fire alarm inspection satisfactory for exit corridor, women's lockers and restrooms, and southeast portion of area C.
INSP-Conference5/31/20056/1/20056/1/2005ADONE
DetailsForrest France
Done. Walk through with Phil Doble and Dave Hannah area C. Discussed project phasing and inspection schedule.