Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR05-00248
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 12550 W EXPLORER DR
Project NameSPR UG ALPINE BUILDING
Customer Number 
ePlanReview 
Description
ALPINE BUILDING (SHELL & CORE) - To install approximately 120'-0" of 6" C-900 PVC from a point west of this proposed building, running northeast around the back and west into a specified Mechanical Room (#108) with 6' Ductile Iron with an M.J. X Flange adapter, approximately 6" above finished floor grade for an underground fire service supply in a new 22,315-ft/2, two story, concrete tilt-up office shell and core building. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD04-02346.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/30/200512/30/200512/30/2005PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro9/7/20059/9/20059/9/2005APART
DetailsForrest France
Hydrostatic test of the UG fire supply line passed inspection. Flushing of the UG supply performed after the hydro was also satisfactory.
INSP-Sprinkler Rough-in5/11/20055/11/20055/11/2005PPART
DetailsTroy Cobbley
Inspection was for underground cover. Piping matches resubmitted plans and is ok to cover.
INSP-Sprinkler Rough-in5/10/20055/10/20055/10/2005PFAIL
DetailsTroy Cobbley
Concrete truck had mechanical problem and couldn't make it till possibly the end of the day and the truck for the bedding had not shown up yet. Contractor will reschedule for the morning.
INSP-Sprinkler Rough-in5/9/20055/9/20055/9/2005PCANC
DetailsForrest France
Inspection cancelled per. contractor due to poor weather conditions. Work not ready, will re-schedule.