Permit Information
Permit NumberFIR05-00259
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 4709 W STATE ST
Project NameSPR OH COLLISTER COMMUNITY CH
Customer Number 
ePlanReview 
Description
COLLISTER COMMUNITY CHURCH ADDITION * To install a complete automatic, single, 364 gallon, dry pipe system throughout a 5,640-ft/2, one story, type V-B new addition and a 2,828-ft/2, two story (small 280-ft/2 2nd story classroom), type V-B existing Sanctuary. The fire sprinklers are used for area and additional story in the existing building. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The underground supply was permitted separately under FIR05-00113. This permit is attached to building permit: BLD04-02139.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/22/20059/23/20059/23/2005APASS
DetailsTroy Cobbley
Fire sprinkler finaled. Insulation has been installed in the existing dormers and the standard heads re-installed.
INSP-Final Inspection9/19/20059/20/20059/21/2005AFAIL
DetailsTroy Cobbley
Need hydraulic calcs for the dormer areas
INSP-Final Inspection9/16/20059/16/20059/16/2005PFAIL
DetailsTroy Cobbley
There are still obstructions to the upright sprinkler heads above the ceiling in the existing chapel and I need calculations for the attic heads in the existing dormers.
INSP-Final Inspection9/14/20059/15/20059/15/2005PCANC
DetailsTroy Cobbley
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
INSP-Sprinkler Rough-in/Hydro9/12/20059/12/20059/12/2005PPART
DetailsTroy Cobbley
See approved plans for locations of remaining deficiencies. Also still need head wrench, sign on control valve and forward flush
INSP-Sprinkler Rough-in9/7/20059/9/20059/9/2005ACANC
DetailsForrest France
No time for this inspection today, spoke with Mike from TV to schedule for monday 9/12 per our agreement.
INSP-Sprinkler Rough-in/Hydro8/24/20058/24/20058/24/2005PPART
DetailsForrest France
Dry system 24 hour air test passed with the maximum allowable loss of 1.5 psi, air pressure at 2:00 p.m 8/24/05 was 40.5 psi.
INSP-Sprinkler Rough-in/Hydro8/23/20058/23/20058/23/2005PPART
DetailsForrest France
Begin 24 hour air test of the dry system at 1:55 p.m 8/23/05 at 42psi.
INSP-Sprinkler Rough-in/Hydro8/18/20058/19/20058/19/2005PPASS
DetailsTroy Cobbley
hydro test for overhead passed
INSP-Sprinkler Rough-in/Hydro6/9/20056/10/20056/10/2005APASS
DetailsTroy Cobbley
Sprinkler piping in new addition is ok to cover.
INSP-Sprinkler Rough-in6/7/20056/7/20056/7/2005PPASS
DetailsTroy Cobbley
Tenting in new addition is passed. Storage areas and concealed combustible areas still need addressed
INSP-Sprinkler Rough-in/Hydro6/6/20056/7/20056/7/2005APART
DetailsTroy Cobbley
See city approved plans for locations of deficiencies. Lower system south end not installed yet. Hydro test passed but was only partial test.
INSP-Sprinkler Rough-in/Hydro6/2/20056/3/20056/3/2005AFAIL
DetailsTroy Cobbley
Plans on job site are only have partial approvals. Updated plans are not on site. Could not do hydro because guage only showed 180lbs of pressure. No inspection done.