Permit Information
Permit NumberFIR05-00265
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 6710 SUPPLY WAY
Project NameSPR UG WESTERN TRAILER SHOP
Customer Number 
ePlanReview 
Description
WESTERN TRAILERS UNDERGROUND - To install approximately 90'-0" of C-900 PVC for a new 22,300-ft/2, one story, pre-engineered steel "Butler" shop building. The tap is connected off of Supply Way traveling northeast and east into some point in the building. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD05-00672.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/5/200512/5/200512/5/2005APASS
DetailsForrest France
UG fire supply finaled.
INSP-Alarm Testing11/2/200511/2/200511/2/2005PPASS
DetailsForrest France
Underground fire supply line permit finaled.
INSP-Final Inspection11/2/200511/2/200511/2/2005PCANC
DetailsForrest France
Duplicate inspection already called in.
INSP-Sprinkler Rough-in9/14/20059/15/20059/16/2005PPART
DetailsForrest France
First floor lower office sprinkler rough-in is good for cover, also discussed uprights above drop ceiling at second level and garage door coverage in the warehouse area.
INSP-Sprinkler Rough-in/Hydro6/28/20056/29/20056/29/2005APART
DetailsForrest France
Underground fire supply passed hydrostatic test. Still need to perform UG flushing.
INSP-Sprinkler Rough-in6/22/20056/23/20056/23/2005APART
DetailsForrest France
Underground fire supply line is approved for cover.
INSP-Sprinkler Rough-in6/21/20056/22/20056/22/2005AFAIL
DetailsForrest France
Fail, underground pipe has been buried prior to inspection for cover. Expose pipe and call for a re-inspect.
INSP-Sprinkler Rough-in6/16/20056/16/20056/16/2005PFAIL
DetailsForrest France
Underground piping must meet min. depth of bury req. NFPA 10.4.1, backfill at rock per 10.9.4, support per 10.7.9, distance from embankment per 10.5.4, and meet deflection requirements. The pipe laid over the large section of embeded rock in the trench fails to meet code standards and requirements.
INSP-Sprinkler Rough-in6/13/20056/13/20056/13/2005PPART
DetailsForrest France
Underground fire supply line riser piece and 5' stub out OK to cover. Still need provision for EQ clearance through floor slab.