Permit Information
Permit NumberFIR05-00266
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 111 S 6TH ST
Project NameSPR BOARDING HOUSE
Customer Number 
ePlanReview 
Description
(BOARDING HOUSE-EAST SIDE) This is a limited Scope of Work Permit. The east building will be fully fire sprinklered throughout with a NFPA 13 system for the conversion of an existing historic building to a boarding house (bed & breakfast). Fire sprinkler work includes a 6" C-900 PVC underground fire service supply from South Street, with an outside PIV, running into the basement of the west side building (restaurant). The inside fire sprinkler work includes the riser only in the restaurant and overhead supply main feed into the east side basement, with another system separation control for 5 sleeping units, a porch, entry, 3 bathroom some closets and common areas throughout. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-00011.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/22/200512/22/200512/22/2005PPASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection12/22/200512/22/200512/22/2005PPASS
DetailsForrest France
Fire sprinkler passed final inspection, c/n items are complete.
INSP-Sprinkler Rough-in/Hydro11/17/200511/18/200511/18/2005APART
DetailsForrest France
Overhead hydrostatic test passed inspection.
INSP-Sprinkler Rough-in/Hydro11/17/200511/17/200511/17/2005PFAIL
DetailsForrest France
Hydrostatic test started but failed midway due to pipe breakage per phone call from the GC.
INSP-Sprinkler Rough-in/Hydro11/9/200511/10/200511/10/2005PCANC
DetailsTroy Cobbley
No time for inspection
INSP-Sprinkler Rough-in8/24/20058/24/20058/24/2005PPART
DetailsForrest France
Underground fire supply line stub out to 8' of building is good for cover.
INSP-Sprinkler Rough-in8/17/20058/17/20058/17/2005APART
DetailsForrest France
Underground fire supply line between the restaurant and the boarding house is acceptable to cover with the sleeve installed per Bill Alexander.
INSP-Sprinkler Rough-in8/16/20058/16/20058/16/2005PFAIL
DetailsForrest France
Provide the correct set of approved drawings for this inspection, steel pipe is not allowed for underground fire service applications unless specifically listed.
INSP-Sprinkler Rough-in8/16/20058/17/2005 A 
DetailsForrest France
###-#### - bruce Note: after morning 9:00 ish