Permit Information
Permit NumberFIR05-00267
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 350 N MILWAUKEE ST Unit: 2026
Project NameSPR SPENCER'S BTS - #2026
Customer Number 
ePlanReview 
Description
(SPENCER'S)(BOISE TOWNE SQUARE-SPACE #2026) To modify and existing OH-2 fire sprinkler system in the remodel of an existing 1,927-ft/2 tenant space, located on the second floor. Fire sprinkler work is related to construction of a new noncombustible partition wall to separate storage area from retail area, one restroom and new storefront with roll down security grill. This building is fully fire sprinklered and contains a smoke evacuation system. This fire protection work shall comply with the IFC 2000 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-00736.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/6/20059/7/20059/7/2005APASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection8/31/20059/1/20059/1/2005AFAIL
DetailsForrest France
Incomplete coverage at front of store next to entryway, upright head is blocked by a soffit below.
INSP-Conference8/16/20058/16/20058/16/2005PDONE
DetailsTroy Cobbley
I spoke to Jeff at treasuer valley fire and he will follow up on status of the fire sprinkler permit
INSP-Final Inspection5/31/20055/31/20055/31/2005PPART
DetailsTroy Cobbley
Piping still does not match plans. Per sam rogers a temp is ok until plans have been resubmitted
INSP-Final Inspection5/24/20055/24/20055/24/2005PCANC
DetailsTroy Cobbley
Per Adam the plans have not been resubmitted yet as requested at the last inspection
INSP-Final Inspection5/20/20055/20/20055/20/2005PFAIL
DetailsTroy Cobbley
Resubmit plans showing the correct floor plan, main location, piping size and deletion of head at front of store. Provide sprinkler coverage in the entry since entry soffit and overhead duct combined exceed 4'.
INSP-Sprinkler Rough-in/Hydro5/18/20055/19/20055/19/2005ACANC
DetailsTroy Cobbley
To be done when building is ready to final.