Permit Information
Permit NumberFIR05-00272
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 2460 -2502 N BOGUS BASIN RD
Project NameSPR HIGHLANDS VILLAGE BLD 8
Customer Number 
ePlanReview 
Description
HIGHLANDS VILLAGE BLD #8 * 2460, 2462, 2502 N. Bogus Basin Rd. To install approximately 90'-0" of 4" C-900 PVC on the north and around the east side south, and up with a 4" D.I. riser piece to approximately 6" above concrete floor grade and to install overhead fire sprinkler protection throughout a new 13,266-ft/2 three story, four unit apartment building. The first floor is 4,346-ft/2 of which 2,912-ft/2 is for the garages (protected to Ordinary Group design) and the remaining is common area, (Light Hazard design). The second floor is 4,440-ft/2 and the third floor is 4,440-ft/2. These residential floors will be protected with a 13R design. Each unit on the second and third floors are single story units. This building is fire sprinklered per NFPA 13R for story increase. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work. This permit is attached to building permit: BLD04-0943.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/9/200610/10/200610/10/2006APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection10/5/200610/6/200610/6/2006ACANC
DetailsTroy Cobbley
No time left in day for inspection
INSP-Sprinkler Rough-in/Hydro9/8/20069/11/20069/11/2006PPART
DetailsForrest France
AG hydrostatic test passed.
INSP-Sprinkler Rough-in/Hydro9/7/20069/8/20069/8/2006PCANC
DetailsTroy Cobbley
No time for the hydro test today
INSP-Sprinkler Rough-in4/11/20064/12/20064/13/2006APART
DetailsForrest France
Reducing bushing near the first floor riser and above the 3rd floor southeast master bathroom are not engaged properly in the fitting socket , elevator shaft heads are not installed at this time, the 2nd floor riser main is exposed in a closet-need to conceal or provide protection, possible light fixture obstruction at the 2nd floor west elevator lobby, no cover is allowed on the 3rd floor until a tenting inspection has been completed for cold cavity protection.
INSP-Sprinkler Rough-in4/10/20064/11/20064/11/2006PCANC
DetailsForrest France
No time available for this inspection today, to be rescheduled per agreement with contractor.
INSP-Sprinkler Rough-in/Hydro6/30/20056/30/20056/30/2005PPART
DetailsForrest France
UG rough-in resubmit, hydro test, and flushing preformed satisfactory.
INSP-Supply line flush6/30/20056/30/20056/30/2005PPART
DetailsForrest France
UG flush is okay.
INSP-Supply line flush6/15/20056/16/20056/16/2005PFAIL
DetailsForrest France
Installation does not match approved plans, pipe routing has been changed significantly.