INSP-Final Inspection | 3/21/2006 | 3/22/2006 | 3/22/2006 | A | PASS |
Forrest France
|
|
|
c/n items have been completed, fire sprinkler permit passed inspection.
|
INSP-Final Inspection | 3/16/2006 | 3/17/2006 | 3/17/2006 | A | PART |
Forrest France
|
|
|
Items on previous correction notice have been completed, per state elevator requirements the wood framed sheetrocked shaft is considered combustible and will require a sprinkler at the top.
|
INSP-Final Inspection | 3/10/2006 | 3/16/2006 | 3/16/2006 | A | FAIL |
Forrest France
|
|
|
Missing escutcheons at some locations, provide flex coupling at riser, provide tags on riser, certify backflow preventer, sprinkler related alarms to be verified at next alarm inspection.
|
INSP-Final Inspection | 9/30/2005 | 9/30/2005 | 9/30/2005 | P | FAIL |
Forrest France
|
|
|
The resubmitted plans for field changes still do not match the installation as required, the first floor main and riser room locations are not accurate showing on opposite sides of the building from the actual install.
|
INSP-Sprinkler Rough-in/Hydro | 8/30/2005 | 8/31/2005 | 8/31/2005 | P | PART |
Forrest France
|
|
|
3rd floor (4 dormers) addition and full hydro test.
rick; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
INSP-Sprinkler Rough-in | 8/24/2005 | 8/25/2005 | 8/25/2005 | A | FAIL |
Forrest France
|
|
|
First floor piping does not match approved drawings due to several field changes that have been made, resubmit plans reflecting the actual installation for approval prior to field inspection, the second floor rough-in is good for cover, the third floor master bedrooms each have low soffits affecting proper coverage and response time.
|
INSP-Supply line flush | 6/30/2005 | 6/30/2005 | 6/30/2005 | P | CANC |
Forrest France
|
|
|
Wrong permit number called in, this inspection was for UG under permit fir04-00495.
|
INSP-Sprinkler Rough-in/Hydro | 6/30/2005 | 6/30/2005 | 6/30/2005 | P | CANC |
Forrest France
|
|
|
Wrong permit number called in, this inspection was for UG under permit fir04-00495.
|