INSP-Final Inspection | 4/20/2006 | 4/21/2006 | 4/21/2006 | A | PASS |
Forrest France
|
|
|
Required corrections have been completed, fire sprinkler finaled.
|
INSP-Sprinkler Rough-in/Hydro | 4/17/2006 | 4/18/2006 | 4/18/2006 | A | PASS |
Troy Cobbley
|
|
|
Basement hydro test passed.
|
INSP-Final Inspection | 4/14/2006 | 4/17/2006 | 4/17/2006 | P | FAIL |
Troy Cobbley
|
|
|
Basement hydro test failed again. Balldrip did not operate, riser strickers, riser tag and backflow preventor certification still needs to be done. No final inspection performed.
|
INSP-Sprinkler Rough-in/Hydro | 4/14/2006 | 4/17/2006 | 4/17/2006 | A | FAIL |
Troy Cobbley
|
|
|
Basement hydro test failed again. Balldrip did not operate, riser strickers, riser tag and backflow preventor certification still needs to be done.
|
INSP-Final Inspection | 4/13/2006 | 4/14/2006 | 4/17/2006 | P | NR |
Forrest France
|
|
|
Project is not ready for final inspection.
|
INSP-Sprinkler Rough-in/Hydro | 4/13/2006 | 4/14/2006 | 4/14/2006 | A | PART |
Troy Cobbley
|
|
|
Fourth floor hydro test passed. Basement hydro test failed.
|
INSP-Final Inspection | 4/13/2006 | 4/14/2006 | 4/13/2006 | A | CANC |
Forrest France
|
|
|
Contact: Jason; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|
INSP-Sprinkler Rough-in/Hydro | 4/5/2006 | 4/6/2006 | 4/6/2006 | A | FAIL |
Forrest France
|
|
|
Overhead hydrostatic test failed to maintain pressure on the 4th floor and the standpipe, basement system not tested at this time.
|
INSP-Sprinkler Rough-in/Hydro | 3/28/2006 | 3/29/2006 | 3/29/2006 | A | FAIL |
Forrest France
|
|
|
Flexible couplings are required on the 4" riser main above and below each floor penetration as the min. seismic clearance is not provided at these locations, the min. separation for heads at the east corner of each floor is exceeded.
|
INSP-Sprinkler Rough-in | 9/15/2005 | 9/16/2005 | 9/16/2005 | A | FAIL |
Forrest France
|
|
|
Coverage is lacking under stairs at first floor, 3/4 upright heads in four locations as marked on approved plans exceed minimum spacing allowance, some sprigs at first floor corridor are not vertical, elevator pit needs the sw heads and cages installed, verify heads in stairway are 155 degree, pipe drain from ball drip at west FDC to an approved location, the riser and ceilings in exit corridors are not complete yet, this inspection was for BODO 4 two story building.
|
INSP-Sprinkler Rough-in/Hydro | 9/15/2005 | 9/15/2005 | 9/15/2005 | P | CANC |
Forrest France
|
|
|
Inspection has been rescheduled for friday am 9/16/05.
|
INSP-Supply line flush | 9/15/2005 | 9/15/2005 | 9/15/2005 | P | PART |
Forrest France
|
|
|
UG fire supply line flush is satisfactory.
|