Description |
To provide total area automatic detection and notification in the TI space. The TI space is in a double interlock "pre-action" zone that is controlled by the FACP. The FACP is being re-programmed to accommodate the proper sequence for a double inter-lock system. (The first initiating point is a single smoke detector - second initiating point is the loss of pressure for solenoid valve release.)
The associated building permit (BLD 05-01139) is to remodel an existing 2,030 sq ft office space per approved plans. Work to include, construction of partitions to create two small office spaces, a small conference room and an open office area, all lights are being relocated, new bi-level switching requirements, and a new window is being installed in the existing corridor, (this corridor is not required to be rated under the 2003 IBC), This building is fully fire sprinklered with quick response sprinkler heads, any alterations to the sprinkler system shall be per NFPA #13 as regulated by the fire department. A separate permit will be required for any sprinkler work. rmh *(Solution Pro / Quail Court Bld)*
|