INSP-Final Inspection | 7/25/2005 | 7/25/2005 | 7/25/2005 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Final Inspection | 7/19/2005 | 7/21/2005 | 7/21/2005 | A | PART |
Forrest France
|
|
|
Work is satisfactory, final pending sign-off on shell permit FIR05-00111.
|
INSP-Sprinkler Rough-in/Hydro | 7/5/2005 | 7/6/2005 | 7/6/2005 | A | FAIL |
Forrest France
|
|
|
Provide proper temp. head at location directly in front at soffit above recessed fireplace to meet req. of NFPA table 6.2.5.1.
|
INSP-Sprinkler Rough-in/Hydro | 6/30/2005 | 7/5/2005 | 7/5/2005 | A | CANC |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 6/30/2005 at 3:27:53 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jul 5 2005 7:07AM.
|
INSP-Sprinkler Rough-in/Hydro | 6/22/2005 | 6/23/2005 | 6/23/2005 | A | FAIL |
Forrest France
|
|
|
Attatch missing retaining straps at two locations, clamp down retaining strap at end line east side, need 200 degree head in medical gas storage closet.
|