INSP-Final Inspection | 2/14/2006 | 2/15/2006 | 2/15/2006 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 2/7/2006 | 2/7/2006 | 2/7/2006 | P | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given with Dave Hannemans permission until issues with the shell building have been corrected.
|
INSP-Final Inspection | 2/2/2006 | 2/3/2006 | 2/3/2006 | P | FAIL |
Troy Cobbley
|
|
|
Provide approved hangers for th 4" main. Provide correct attachment for the eq bracing. Provide forward flush. Provide review comments. Provide correct air compressor and air maintenance device.
|
INSP-Sprinkler Rough-in | 1/25/2006 | 1/26/2006 | 1/26/2006 | P | PASS |
Troy Cobbley
|
|
|
Sprinkler piping in the second floor attic and the east tenant improvement space are ok for cover
|
INSP-Sprinkler Rough-in | 1/17/2006 | 1/19/2006 | 1/19/2006 | A | PART |
Troy Cobbley
|
|
|
The south wing piping in the attic area is ok to cover with insulation
|
INSP-Supply line flush | 1/4/2006 | 1/5/2006 | 1/5/2006 | A | PASS |
Troy Cobbley
|
|
|
Underground flush passed
|
INSP-Supply line flush | 1/4/2006 | 1/4/2006 | 1/4/2006 | P | FAIL |
Troy Cobbley
|
|
|
united water did not show up
|
INSP-Sprinkler Rough-in | 12/9/2005 | 12/12/2005 | 12/12/2005 | A | FAIL |
Troy Cobbley
|
|
|
No inspection is supposed to be called in but I did it anyway. Alot of changes have taken place with the piping. Per fitter these changes are reflected on another resubmittal that is in for review. This includes heads repiped and added in the second floor dry remote area, branchline added on the lower level dry system and main reroutes. Dry system heads dont meet 8.6.5.2.1.6 for spacing.
|
INSP-Sprinkler Rough-in | 11/22/2005 | 11/23/2005 | 11/22/2005 | P | CANC |
Troy Cobbley
|
|
|
No time for inspection
|
INSP-Sprinkler Rough-in | 11/21/2005 | 11/22/2005 | 11/22/2005 | A | CANC |
Troy Cobbley
|
|
|
No time for inspection
|
FIR-Aging Inspection | 9/8/2005 | 9/8/2005 | 9/13/2005 | | NR |
Troy Cobbley
|
|
|
Work is in progess. Job only has a partial approval. Resubmittals required.
|