Permit NumberFIR05-00326
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 117 S 6TH ST
Project NameSPR LEKU ONA-RESTAURANT
Customer Number 
ePlanReview 
Description
(LEKU ONA) This is a limited "Scope of Work Permit", which is fire sprinkling the existing portion of the west building (2 story with basement) and new construction of a 3,024-ft/2 addition which includes 6 restrooms, an elevator, stairways, interior walls, steel beams, wood columns, steel columns, seismic upgrade. This work is related to the conversion of an existing 6,027-ft/2 building into a restaurant / bar occupancy. This building is fire sprinklered for area increase; story increase; to allow the basement to be unenclosed; to allow corridors to be nonrated; and to allow the basement, 1st story, and 2nd story to be open to each other. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The east building (Boarding House-East Structure) and underground supply is permitted under FIR05-00226 attached to building permit BLD05-00011. This permit is attached to building permit BLD05-00458.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/21/200511/22/200511/22/2005APASS
DetailsForrest France
Correction notice items have been completed, submit as-builts reflecting pipe routing changes as required.
INSP-Final Inspection11/16/200511/17/200511/17/2005APART
DetailsForrest France
Correction notice items have been completed, final pending forward flow, alarms, ceiling tile and canopies, and fill the annular space at UG penetration.
INSP-Final Inspection11/15/200511/15/200511/15/2005PFAIL
DetailsForrest France
Fail inspection due to numerous issues still not corrected, a 13 item c/n was left with Nick of Guho const., not all items inspected at this time-third floor not inspected as well.
INSP-Final Inspection11/14/200511/14/200511/14/2005PCANC
DetailsForrest France
Out of time, no inspection performed.
INSP-Final Inspection11/9/200511/10/200511/10/2005PCANC
DetailsTroy Cobbley
no time for inspection
INSP-Supply line flush11/2/200511/3/200511/3/2005PFAIL
DetailsForrest France
Provide resubmittals as required indicating information as requested on plan review notes and all field changes from original plans, overhead inspection failed due to numerous issues including spacing, head temps., bracing, seismic clearance, obstructions to discharge, riser not complete, etc., the UG was flush was performed and is acceptable.
INSP-Sprinkler Rough-in/Hydro10/31/200511/1/200511/1/2005PPART
DetailsForrest France
Overhead and underground hydrostatic tests are satisfactory.
INSP-Sprinkler Rough-in/Hydro10/26/200510/28/200510/28/2005ACANC
DetailsForrest France
No time available for this inspection today due to BODO projects.
INSP-Sprinkler Rough-in9/8/20059/8/20059/8/2005PPART
DetailsForrest France
The upright heads above hard lid areas on 2nd floor hall in front of the restrooms are okay to cover.