Permit Information
Permit NumberFIR05-00338
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 10051 W EMERALD ST
Project NameSPR UG EMERALD TECH #11
Customer Number 
ePlanReview 
Description
EMERALD TECH CENTER - BUILDING #11 (SHELL UNDERGROUND) - To install approximately 150'-0" of 6" C-900 PVC underground connected at the property line on the west side of N. Ancestor Place, running west 130'-0", then north 20'-0", under the footing and up through the floor with Class 50 Ductile Iron to approximately 6" above finished floor grade, with a 6" X 11½" adapter. This service supply is for the fire protection needs in a 13,140-ft/2, one story concrete tilt-up exterior walls, steel roof system, office and storage shell building with a 140-ft/2 mechanical room at the south side of the building. This will be a shell building. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD05-00916.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/9/200610/9/200610/9/2006PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Supply line flush9/1/20059/2/20059/2/2005APART
DetailsForrest France
UG fire line flush is satisfactory. Advised contractor that the depth of bury still appears too shallow, however, site work is not complete. Will verify before final approval that the depth of cover is sufficient.
INSP-Sprinkler Rough-in/Hydro9/1/20059/2/20059/2/2005APART
DetailsForrest France
Hydrostatic test of the underground fire supply line passed. Although the site work is not completed, depth of bury still appears too shallow as evidenced by my mark on an adjacent concrete vault.
INSP-Sprinkler Rough-in8/26/20058/29/20058/29/2005AFAIL
DetailsForrest France
Underground fire supply line installation does not match the approved drawings. Need to resubmit plans reflecting added 45's and change of directions for approval prior to field inspection. In addition, the minimum 4'-6" depth of bury is not met in several locations.
INSP-Sprinkler Rough-in8/26/20058/26/20058/26/2005PCANC
DetailsForrest France
Canceled inspection, will schedule for monday the 29th.