INSP-Final Inspection | 10/26/2005 | 10/27/2005 | 10/27/2005 | A | PASS |
Forrest France
|
|
|
Fire sprinkler passed inspection.
|
INSP-Final Inspection | 10/26/2005 | 10/26/2005 | 10/26/2005 | A | FAIL |
Forrest France
|
|
|
Review notes were not available on site for inspection, escutcheons are missing in three locations
|
INSP-Sprinkler Rough-in/Hydro | 10/13/2005 | 10/13/2005 | 10/13/2005 | P | PART |
Forrest France
|
|
|
Hydrostatic test of antifreeze system passed inspection.
|
INSP-Sprinkler Rough-in/Hydro | 10/10/2005 | 10/11/2005 | 10/11/2005 | P | CANC |
Troy Cobbley
|
|
|
Contact: Brian - Hydro Test; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
|
INSP-Sprinkler Rough-in | 10/10/2005 | 10/11/2005 | 10/11/2005 | A | PART |
Troy Cobbley
|
|
|
Provide 200 degree pendant in the utility room, finish installing ceiling and canopies, provide longitudinal bracing on the antifreeze main under canopy. Per Bill the 130 sq. ft. max spacing is a type error. 225 sq. ft. is allowed in the light hazard areas.
|
INSP-Sprinkler Rough-in | 9/22/2005 | 9/22/2005 | 9/22/2005 | P | PART |
Forrest France
|
|
|
Overhead rough-in is okay for cover in the grid ceiling areas, will verify proper spacing and head temp. ratings at heat sources in the kitchen after all drops have been cut in. One branch line is directly over an electrical panel, this will need to be relocated per electrical code.
|
INSP-Sprinkler Rough-in | 8/19/2005 | 8/19/2005 | 8/19/2005 | A | PART |
Forrest France
|
|
|
Rough-in areas above hard lids are okay to cover, need to cut head in southwest soffit as discussed, GC to provide drop ceiling in storage room, antifreeze system is not complete or inspected at this time.
|
INSP-Sprinkler Rough-in/Hydro | 8/18/2005 | 8/19/2005 | | A | |
Unknown
|
|
|
Contact: Jim - Cover Inspection; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
|
INSP-Sprinkler Rough-in/Hydro | 8/10/2005 | 8/12/2005 | | A | |
Unknown
|
|
|
Contact: Brian Calkins - Rough In; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
|