Permit Information
Permit NumberFIR05-00390
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 999 N CURTIS RD
Project Namealm - SAMC Peds ref temp mon
Customer Number 
ePlanReview 
Description
To provide temperature monitoring of a refrigerator in the pediatrics unit located in room 476 on the 4th floor. The FACP is located in the basement. A sequence of operation is included in the fire alarm permit set that defines the input as a "priority 2". This would be considered a "combination system" and all fire alarm signals would override the monitoring input. Battery calculations look sufficient for the FACP. No written comments. The PDS Fire Inspector shall field verify the fire alarm signals to override the monitoring signal.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/30/20059/2/20059/2/2005ADONE
DetailsForrest France
Scheduled by a contractor via Hello! on 8/30/2005 at 5:08:48 PM. Contact: ###-####.
DOC - Permit Finaled  9/2/2005 DONE
Verified input signal to FACP, control room and remote annunciator. Signal is a supervisory.
INSP-Final Inspection8/30/20058/30/20058/30/2005PCANC
DetailsForrest France
No time to perform this inspection today. Orlen to reschedule for this friday per our agreement.